YASKAWA HV600 Technical Reference page 623

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Setting Value
Function
97
Low Feedback
9E
Low PI Auxiliary Control
Level
9F
High PI Auxiliary Control
Level
A9
RELAY Operator Control
AB
Thrust Mode
AC
Setpoint Not Maintained
B2
BAS Interlock
B8
Pump Fault
B9
Transducer Loss
BA
PI Auxiliary Control
Active
BB
Differential Feedback
Exceeded
BC
Sleep Active
BD
Start Delay
BE
Pre-Charge
C0
HAND Mode
C1
AUTO Mode
C2
OFF Mode
C3
Main Feedback Lost
C4
Backup Feedback Lost
100
!During Run
101
!Zero Speed
102
!Speed Agree 1
103
!User-Set Speed Agree 1
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
The terminal activates when the drive is in a Low Feedback Condition as specified by Y1-08 [Low Feedback Level]
and Y1-09 [Low Feedback Lvl Fault Dly Time] and when the drive detects an LFB [Low Feedback Sensed] fault or an
LOFB [High Feedback Sensed] alarm.
The terminal activates when the PI Aux Feedback Level is less than YF-09 [PI Aux Control Low Level Detect] or if the
drive detects an LOAUX [Low PI Aux Feedback Level] fault.
The terminal activates when the PI Aux Feedback Level is more than YF-12 [PI Aux Control High Level Detect] or if
the drive detects an HIAUX [High PI Aux Feedback Level] fault.
The terminal changes to OFF or ON when you push the RELAY (
to turn it OFF. When the terminal is OFF, push
The terminal activates when the output frequency is between 0.0 Hz and the value set in Y4-12 [Thrust Frequency] and
the Thrust Bearing function is active.
The terminal activates when the drive detects NMS [Setpoint Not Met] condition.
The terminal activates when the Run command is active or the drive is outputting the voltage. The drive will use this
as an actuation signal for an external damper.
The terminal activates when one of these faults is active: LFB [Low Feedback Sensed], HFB [High Feedback Sensed],
NMS [Setpoint Not Met], or EFx [External Fault (Terminal Sx)].
The terminal activates when the current into the analog input associated with PID feedback is more than 21 mA or less
than 3 mA, or an FDBKL [WIRE Break] Fault or an FDBKL [Feedback Loss Wire Break] Alarm is active.
The terminal activates when the PI Auxiliary Controller has an effect on the output speed.
The terminal activates when the difference between the PID Feedback and the value from the terminal set for H3-xx =
2D [Differential Feedback] is more than Y4-18 [Differential Level] for the time set in Y4-19 [Differential Lvl
Detection Time].
The terminal activates when the Sleep function is active and the drive is not operating.
Note:
The terminal will not activate for Sleep Boost function.
The terminal activates when the Feedback is more than the start level or the Feedback is less than the Inverse PID and
the start timer is timing.
Note:
You must set Y1-04 [Sleep Wake-up Level] ≠ 0 and Y1-05 [Sleep Wake-up Level Delay Time] ≠ 0 to use this
function.
The terminal activates when the drive is in Pre-Charge Mode.
The terminal activates when the drive is in HAND Mode operation.
The terminal activates when the drive is in AUTO Mode operation.
The terminal activates when the drive is in OFF Mode operation.
The terminal activates when the drive loses the main PID feedback.
The terminal activates when the drive loses the backup PID feedback.
The terminal deactivates when you input a Run command and when the drive is outputting voltage.
ON : Drive is stopping
OFF : Drive is running
The terminal deactivates when the output frequency < E1-09 [Minimum Output Frequency].
ON : Output frequency ≥ value of E1-09.
OFF : Output frequency < value of E1-09.
The terminal deactivates when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree
Detection Width].
Note:
The detection function operates in the two motor rotation directions.
ON : The output frequency does not align with the frequency reference although the drive is running.
OFF : The output frequency is in the range of "frequency reference ± L4-02".
The terminal deactivates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02
[Speed Agree Detection Width] and in the range of the frequency reference ± L4-02.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
ON : The output frequency is not in the range of "L4-01 ± L4-02" or the range of frequency reference ± L4-02.
OFF : The output frequency is in the range of "L4-01 ± L4-02" and the range of frequency reference ± L4-02.
9.10 H: Terminal Functions
Description
) button. When the terminal is ON, push
to turn in ON.
Ref.
291
291
291
291
291
291
292
292
292
292
292
292
292
292
292
293
293
293
293
293
293
293
293
9
623