Advertisement

5.10 o: Keypad-Related Settings
No.
Item
1
Attribute
2
File number
3
Time stamp
4
Log Monitor Data 1
5
Log Monitor Data 2
:
:
13
Log Monitor Data 10
14
Reserved
15
Encoding data
16
File number
o5-01: Log Start/Stop Selection
No.
Name
(Hex.)
o5-01
Log Start/Stop Selection
(1551)
RUN
Note:
You must insert a compatible SD cart into the keypad before you enable this parameter.
0 : OFF
Stops the data log.
1 : ON
Starts the data log as specified by the sampling cycle set in o5-02 [Log Sampling Interval].
o5-02: Log Sampling Interval
No.
Name
(Hex.)
o5-02
Log Sampling Interval
(1552)
RUN
o5-03: Log Monitor Data 1
No.
Name
(Hex.)
o5-03
Log Monitor Data 1
(1553)
RUN
Note:
Set the U monitor number you want to log.
For example, to display U1-01 [Frequency Reference], set o5-03 = 101. When it is not necessary to set a data log monitor, set this parameter
to 000.
372
Number of
Characters
2
[02] shows that the record is a monitor data record.
4
The [xxx] part of the [GLOG0xxx.csv] filename is a 3-digit decimal number in hexadecimal format.
12
Data log data was retrieved (YYMMDDHHMMSS)
4
Monitor number selected by o5-03 [Log Monitor Data 1]
4
Monitor number selected by o5-04 [Log Monitor Data 2]
:
:
4
Monitor number selected by o5-12 [Log Monitor Data 10]
4
-
4
Encoding data for log monitor data 1 through 10 (Hex.)
Bits 0 through 9 show the encoding of log monitor data 1 1 through 10. A bit value of 1 shows that the data represents a
negative value. (Log monitor data 1 through 10 is absolute value data without encoding)
Example when log monitor data 2, 5, and 8 show negative values: Bits 1, 4, and 7 have values of 1, and the encoding data
= 0010010010 (Bin.) = 0092 (Hex.)
6
Row number (Hex.) in the data log file
Sets the data log function. This parameter is only available on an HOA keypad.
Sets the data log sampling cycle. This parameter is only available on an HOA keypad.
Sets the data log monitor. This parameter is only available on an HOA keypad.
Description
Description
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
(Range)
0
(0 - 1)
Default
(Range)
100 ms
(100 - 60000 ms)
Default
(Range)
101
(000, 101 - 1299)