YASKAWA HV600 Technical Reference page 427

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

YF-19: PI Aux Ctrl Feedback WireBreak
No.
Name
(Hex.)
YF-19
PI Aux Ctrl Feedback
WireBreak
(3F62)
0 : Disabled
1 : Alarm Only
The keypad will show an AUXFB [PI Aux Feedback Level Loss] alarm.
2 : Fault (no retry, coast to stop)
When the drive is in AUTO, HAND, or Sleep mode, the keypad will show an AUXFB [PI Aux Feedback Level Loss]
fault.
Note:
If the drive has not received a Run command, the keypad will only show an AUXFB alarm.
YF-20: PI Aux Main PI Speed Control
No.
Name
(Hex.)
YF-20
PI Aux Main PI Speed
Control
(3F63)
0 : Disabled
1 : Enabled
YF-21: PI Aux Ctrl Level Unit Selection
No.
Name
(Hex.)
YF-21
PI Aux Ctrl Level Unit
Selection
(3F64)
0 : "WC: inches of water column
1 : PSI: pounds per square inch
2 : GPM: gallons/min
3 : °F: Fahrenheit
3
4 : ft
/min: cubic feet/min
5 : m
3
/h: cubic meters/hour
6 : L/h: liters/hour
7 : L/s: liters/sec
8 : bar: bar
9 : Pa: Pascal
10 : °C: Celsius
11 : m: meters
12 : ft: feet
13 : L/min: liters/min
14 : m
3
/min: cubic meters/min
15 : "Hg: Inch Mercury
16 : kPa: kilopascal
48 : %: Percent
49 : Custom (YF-32~34)
50 : None
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Sets how the analog input selected for PI Aux Feedback will respond when it is programmed to
receive a 4 mA to 20 mA signal and the signal is lost.
Sets if the PI Auxiliary Controller has an effect on output speed.
Set the units shown for the PI Aux Level parameters and monitors.
5.13 Y: Application Features
Description
Description
Description
Default
(Range)
2
(0 - 2)
Default
(Range)
1
(0, 1)
Default
(Range)
1
(0 - 50)
5
427