5.13 Z: Bypass Parameters
Controls the behavior of the bypass phase rotation detection when operating in Bypass Mode.
Note:
Parameter available in bypass controller software versions VST800298 and later.
No.
Z1-52
Setting 0: Disabled
Setting 1: Alarm
Setting 2: Fault
u

Z2: Bypass Control Input/Output

n
Z2-01 to Z2-08: Digital Input 1 to 8 Function Select
No.
Z2-01
Z2-02
Z2-03
Z2-04
Z2-05
Z2-06
Z2-07
Z2-08
n
Bypass Digital Input Terminal Settings
Setting
Unused (Available for Serial Comms)
Note:
Multiple digital input terminals can
be programmed for "Unused
(Available for Serial Comms)"
(Z2-0o = 0). The drive will run only
<1>
0
when all digital inputs programmed
for "0" are active. This feature
applies to settings 0 and 22. Set all
other selections only once in
parameters Z2-01 to Z2-08.
3
DRV Multi-Function Input S3 (H1-03 Setting)
4
DRV Multi-Function Input S4 (H1-04 Setting)
5
DRV Multi-Function Input S5 (H1-05 Setting)
6
DRV Multi-Function Input S6 (H1-06 Setting)
7
DRV Multi-Function Input S7 (H1-07 Setting)
<2>
DRV Multi-Function Input S8 (H1-08 Setting)
8
21
Run (AUTO Mode)
Run Enable (Safety)
Note:
Multiple digital input terminals can
be programmed for "Run Enable
(Safety)" (Z2-0o = 22) in bypass
controller software versions
<1>
22
VST800298 and later. The drive will
run only when all digital inputs
programmed for "22" are active.
This feature applies to settings 0 and
22. Set all other selections only once
in parameters Z2-01 to Z2-08.
<1> Can be set to multiple digital input parameters simultaneously in bypass controller software versions VST800298 and later.
<2> Available in bypass controller software versions VST800299 and later.
174
Name
Bypass Phase Rotation
Name
Digital Input 1 Function Select
Digital Input 2 Function Select
Digital Input 3 Function Select
Digital Input 4 Function Select
Digital Input 5 Function Select
Digital Input 6 Function Select
Digital Input 7 Function Select
Digital Input 8 Function Select
Table 5.30 Bypass Digital Input Terminal Settings
Function
Page
Setting
23
Run Interlock (BAS)
24
Remote Transfer to Bypass
25
Smoke Purge Bypass Run to Destruction
Smoke Purge Drive Run to Destruction at Smoke
175
26
Purge Preset Speed
27
Motor OR Select
28
Motor AND Select
29
Motor 1 Overload Contact
175
30
Motor 2 Overload Contact
175
31
HAND Select
175
32
AUTO Select
175
33
DRIVE/BYPASS Select
175
34
Fault Reset
35
External Fault (EF0)
175
36
External Fault (EFB)
175
175
YASKAWA SIEP YAIP1B 01B YASKAWA AC Drive – P1000 Bypass Technical Manual
Setting Range
0 to 2
Setting Range
0 to 36
0 to 36
0 to 36
0 to 36
0 to 36
0 to 36
0 to 36
0 to 36
Function
Default
1
Default
21
22
23
24
25
0
0
29
Page
175
175
175
175
175
175
175
175
176
176
176
176
176
176