YASKAWA HV600 Technical Reference page 387

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

S3-03: PI2 Control Decimal Place Pos
No.
Name
(Hex.)
S3-03
PI2 Control Decimal Place
Pos
(321C)
RUN
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
S3-04: PI2 Control Unit Selection
No.
Name
(Hex.)
S3-04
PI2 Control Unit Selection
(321D)
RUN
0 : "WC: inches of water column
1 : PSI: pounds per square inch
2 : GPM: gallons/min
3 : °F: Fahrenheit
4 : ft
3
/min: cubic feet/min
3
5 : m
/h: cubic meters/hour
6 : L/h: liters/hour
7 : L/s: liters/sec
8 : bar: bar
9 : Pa: Pascal
10 : °C: Celsius
11 : m: meters
12 : ft: feet
13 : L/min: liters/min
3
14 : m
/min: cubic meters/min
15 : "Hg: Inch Mercury
16 : kPa: kilopascal
48 : %: Percent
49 : Custom(S3-18~20)
50 : None
S3-05: PI2 Control Setpoint
No.
Name
(Hex.)
S3-05
PI2 Control Setpoint
(321E)
RUN
Note:
Parameters S3-04 [PI2 Control Unit Selection], S3-03 [PI2 Control Decimal Place Pos], and S3-02 [PI2 Control Transducer Scale] set the
unit, resolution, and upper limit.
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Sets the decimal place display for secondary PI units.
Sets the units displayed for the PI2 Control parameters and monitor.
Sets the PI2 Control target setpoint.
5.11 S: Special Applications
Description
Description
Description
Default
(Range)
2
(0 - 3)
Default
(Range)
48
(0 - 50)
5
Default
(Range)
0.00
(0.00 - 600.00)
387