YASKAWA HV600 Technical Reference page 629

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Setting Value
Function
2D
Differential Level Source Enters a feedback value to calculate the Differential Level between the Differential Level Source feedback and the
2E
HAND Frequency Ref or
Setpoint
H4: Analog Outputs
No.
Name
(Hex.)
H4-01
Terminal FM Analog
Output Select
(041D)
H4-02
Terminal FM Analog
Output Gain
(041E)
RUN
H4-03
Terminal FM Analog
Output Bias
(041F)
RUN
H4-04
Terminal AM Analog
Output Select
(0420)
H4-05
Terminal AM Analog
Output Gain
(0421)
RUN
H4-06
Terminal AM Analog
Output Bias
(0422)
RUN
H4-07
Terminal FM Signal
Level Select
(0423)
H4-08
Terminal AM Signal
Level Select
(0424)
H4-20
Analog Power Monitor
100% Level
(0B53)
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
primary PID Feedback [H3-xx = B].
Note:
The full-scale of the analog signal goes from b5-71 [Min PID Transducer Scaling] to b5-38 [PID User Unit
Display Scaling].
Enters the S5-05 [HAND Frequency Reference] value or the S5-06 [HAND Setpoint] value. When S5-01 = 0 [HAND
Frequency Reference Source = HAND Analog Input] and S5-03 = 0 [HAND Mode PI Selection = Disabled], the drive
enters HAND Frequency Reference. When b5-01 ≠ 0, S5-01 = 0, and S5-03 = 1 [Enabled], the drive enters HAND
Setpoint.
Note:
• When PID is enabled, the full-scale of the analog signal goes from b5-71 [Min PID Transducer Scaling] to b5-38
[PID User Unit Display Scaling].
• When PID is disabled, the drive enters this analog signal as the percentage of the E1-04 [Maximum Output
Frequency] value.
Description
Sets the monitor number to send from MFAO terminal FM.
Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-01 = 102 to monitor U1-02
[Output Frequency].
Sets the gain of the monitor signal that is sent from MFAO terminal FM.
Sets the analog signal output level from the terminal FM at 10 V or 20 mA as 100% when
an output for monitoring items is 100%.
Sets the bias of the monitor signal that is sent from MFAO terminal FM.
Set the level of the analog signal sent from terminal FM at 10 V or 20 mA as 100% when
an output for monitoring items is 0%.
Sets the monitoring number to be output from the MFAO terminal AM.
Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-04 = 103 to monitor U1-03
[Output Current].
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
When an output for monitoring items is 0%, this parameter sets the analog signal output
level from the AM terminal at 10 V or 20 mA as 100%.
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
When an output for monitoring items is 0%, this parameter sets the analog signal output
level from the AM terminal at 10 V or 20 mA as 0%.
Sets the MFAO terminal FM output signal level.
Note:
Set jumper S5 on the control circuit terminal block accordingly when you change this
parameter.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
Sets the MFAO terminal AM output signal level.
Note:
Set jumper S5 on the control circuit terminal block accordingly when you change this
parameter.
0 : 0 to 10 Vdc
2 : 4 to 20 mA
Sets the level at 10 V when you set U1-08 [Output Power] for analog output.
9.10 H: Terminal Functions
Description
Ref.
302
303
Default
Ref.
(Range)
102
304
(000 - 999)
100.0%
304
(-999.9 - +999.9%)
0.0%
305
(-999.9 - +999.9%)
103
305
(000 - 999)
50.0%
305
(-999.9 - +999.9%)
0.0%
305
(-999.9 - +999.9%)
0
305
(0, 2)
0
306
(0, 2)
0.00 kW
306
(0.00 - 650.00 kW)
629