YASKAWA HV600 Technical Reference page 402

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

5.11 S: Special Applications
bit 4 : Reserved
bit 5 : oL1 - Motor Overload
bit 6 : oL3 - Overtorque Detection 1
bit 7 : oL4 - Overtorque Detection 2
bit 8 : oL7 - High Slip Braking Overload
bit 9 : Reserved
bit 10 : UL3 - Undertorque Detection 1
bit 11 : UL4 - Undertorque Detection 2
bit 12 : UL6 - Motor Underload
bit 13 : Reserved
bit 14 : oS - Overspeed
bit 15 : dEv: Speed Deviation
Note:
The drive sets the bits in Hex.
S6-13: EMOVR Option Fault ON
No.
Name
(Hex.)
S6-13
EMOVR Option Fault ON
(3244)
Expert
bit 0 : bUS - Option Communication
bit 1 : CE - Communication Error
bit 2 : E5 - SI-T3 Watch Dog Timer
bit 3 : EF0 - Option Card External Fault
bit 4 : PE1 - PLC Fault 1
bit 5 : PE2 - PLC Fault 2
bit 6 : nSE - Node Setup Error
bit 7 to 15 : Reserved
Note:
The drive sets the bits in Hex.
S6-14: EMOVR Application 1 Fault ON
No.
Name
(Hex.)
S6-14
EMOVR Application 1 Fault
ON
(3245)
Expert
bit 0 : EFx - External Faults
bit 1 : Reserved
bit 2 : HLCE - High Level Communications Error
bit 3 : bAT - HOA Keypad Battery Voltage Low
bit 4 : TiM - Keypad Time Not Set
bit 5 : bCE - Bluetooth Communication Fault
bit 6 : Reserved
bit 7 : Reserved
bit 8 : Reserved
bit 9 : MSL - Net Master Lost
402
Sets the bit to enable fault detection during Emergency Override.
Sets the bit to enable fault detection during Emergency Override.
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
(Range)
0
(0 - FFFF)
Default
(Range)
0
(0 - FFFF)

Advertisement

Table of Contents
loading

Table of Contents