5.6 F: Options
Note:
• The following setting values are available when using the PROFINET communication option card (SI-EP3).
–0: Static
–2: DCP
• When F7-13 = 0, set parameters F7-01 to F7-12 [IP Address 1 to Gateway Address 4] to set the IP Address. Be sure to set a different IP
address for each drive on the network.
F7-14: Duplex Mode Selection
No.
Name
(Hex.)
F7-14
Duplex Mode Selection
(03F2)
0 : Half/Half
1 : Auto/Auto
2 : Full/Full
3 : Half/Auto
Port 1 is set to "Half" and port 2 is set to "Auto".
4 : Half/Full
Port 1 is set to "Half" and port 2 is set to "Full".
5 : Auto/Half
Port 1 is set to "Auto" and port 2 is set to "Half".
6 : Auto/Full
Port 1 is set to "Auto" and port 2 is set to "Full".
7 : Full/Half
Port 1 is set to "Full" and port 2 is set to "Half".
8 : Full/Auto
Port 1 is set to "Full" and port 2 is set to "Auto".
F7-15: Communication Speed Selection
No.
Name
(Hex.)
F7-15
Communication Speed
Selection
(03F3)
10 : 10/10 Mbps
100 : 100/100 Mbps
101 : 10/100 Mbps
102 : 100/10 Mbps
Note:
Set this parameter when F7-14 = 0 or 2 [Duplex Mode Selection = Half/Half or Full/Full].
F7-16: Timeout Value
No.
Name
(Hex.)
F7-16
Timeout Value
(03F4)
Note:
Set this parameter to 0.0 to disable the connection timeout function.
258
Sets the duplex mode setting method.
Sets the communications speed.
Sets the detection time for a communications timeout.
Description
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
(Range)
1
(0 - 8)
Default
(Range)
10
(10, 100 - 102)
Default
(Range)
0.0 s
(0.0 - 30.0 s)