Write Automatically Backed-up Parameters to the Bypass

You can automatically back up parameters to the keypad connected to the bypass and write those parameters to a
different drive as specified by the settings of o3-06 [Auto Parameter Backup Selection] and o3-07 [Auto Parameter
Backup Interval].
Note:
• Set o3-06 = 1 [Auto Parameter Backup Selection = Enabled] in each bypass to which you will write the parameters.
• This operation is not available when the parameters in the keypad and the parameters on the other bypasses are set to the same values.
1.
Connect the keypad to the bypass.
2.
Push
or
3.
Push
or
The keypad will show the "End" message when the write process is complete.
166
to select [Yes] and then push
to select [Yes] and then push