10.6 MEMOBUS/Modbus Communications
7.
De-energize the bypass.
8.
Disconnect the jumper from Step 4. Set Z2-06 to its initial function.
Self-Diagnostics is complete and the bypass returns to its usual function.
◆
Communications Data Table
Command Data on page 750
command data, monitor data, and broadcast message.
Refer to the Parameter List for parameter communications registers.
■
Command Data
Note:
When writing a command register that contains reserved bits, always write reserved bits to a "0". Do not write to reserved registers or
monitor registers.
Register No.
(Hex.)
0000
Reserved
Run command, multi-function input command
bit 0
bit 1
bit 2
bit 3
0001
bit 4
bit 5
bit 6
bit 7
bit 8
bit 9
bit A
bit B - F
0002
Frequency reference
0003
Output voltage gain
0004
Torque reference/torque limit (0.1% signed)
0005
Torque compensation (0.1% signed)
0006
PID setpoint (0.01% signed)
0007
Setting for the drive multi-function analog monitor output terminal FM (10 V/4000H)
0008
Setting for the drive multi-function analog monitor output terminal AM (10 V/4000H)
750
and
Monitor Data on page 754
Table 10.30 MEMOBUS/Modbus Communications Command Data
1: Forward run, 0: Stop
1: Run, 0: Stop
1: Reverse run, 0: Stop
1: Reverse, 0: Forward run
External fault
1: EF0 [Option Card External Fault]
Fault Reset Procedure
1: Reset command
Drive Multi-function input 1
Drive Multi-function input 2
Drive Multi-function input 3
Drive Multi-function input 4
Drive Multi-function input 5
Drive Multi-function input 6
Drive Multi-function input 7
Reserved
o1-03 [Frequency Display Unit Selection] (unsigned) sets the units.
Units: 0.1 %
Setting range: 20 (2.0%) to 2000 (200.0%), the default value at energize: 1000 (100.0%)
show the communications data. The data types are
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference