5.14 Z: Bypass Parameters
28: Mirror HV600 M5-M6
Setting Value
Function
28
Mirror HV600 M5-M6
Use H2-03 [Term H2-03 – M5-M6 Function Selection] to set the M5-M6 digital output. Refer to
on page 619
for more information about setting values.
Note:
When the drive unit is OFF (in Bypass Mode in a 3-contactor configured bypass), this output will be OFF.
ON : Digital Output M5-M6 on HV600 is closed
OFF : Digital Output M5-M6 on HV600 is open
99: Not Used
Setting Value
Function
99
Not Used
Z2-30: Analog Input Signal Level Select
No.
Name
(Hex.)
Z2-30
Analog Input Signal Level
Select
(8580)
0 : 0 to 10V (Lower Limit at 0)
2 : 4 to 20 mA
3 : 0 to 20 mA
Z2-32: Analog Input Gain Setting
No.
Name
(Hex.)
Z2-32
Analog Input Gain Setting
(8582)
Z2-33: Analog Input Bias Setting
No.
Name
(Hex.)
Z2-33
Analog Input Bias Setting
(8583)

Z3: Bypass Control Serial Comm

Z3-12: Network Digital Inputs
No.
Name
(Hex.)
Z3-12
Network Digital Inputs
(850B)
0 : Disabled
Serial communications physical digital inputs are ignored.
For MEMOBUS/Modbus (H5-08 = 0): Command Register 8402H is disabled.
For Metasys N2 (H5-08 = 1): Binary Outputs B05, B06, B07, B08, and B09 are disabled.
For P1 Apogee (H5-08 = 2): Points LDO44, LDO45, LDO46, LDO47, and LDO48 are disabled.
For BACnet (H5-08 = 3): BV72, BV73, BV74, BV75, BV76, BV77, BV78, and BV79 are disabled.
1 : Enabled
452
The digital output activates when the HV600 drive digital output (M5-M6) is closed.
This setting allows serial communications to control the output.
Sets the input signal level for MFAI terminal A1.
Sets the gain of the analog signal input to MFAI terminal A1.
Sets the bias of the analog signal input to MFAI terminal A1.
Enables and disables control of the digital inputs over a network. It is not necessary to wire to the
physical digital input.
Description
Description
Description
Description
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
H2: Digital Outputs
Default
(Range)
0
(0 - 3)
Default
(Range)
100.0%
(-999.9 - +999.9%)
Default
(Range)
0.0%
(-999.9 - +999.9%)
Default
(Range)
0
(0, 1)