YASKAWA HV600 Technical Reference page 511

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Code
Name
oPE10
V/f Data Setting Error
Code
Name
oPE11
Carrier Frequency Setting Error
Code
Name
oPE12
Incompatible Drive Software
Code
Name
oPE16
Energy Saving Constants Error
Code
Name
oPE29
Baud Rate Setting Error
Code
Name
oPE33
Digital Output Selection Error
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Causes
The parameters that set the V/f pattern do not satisfy
these conditions:
• E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
[Minimum Output Frequency ≤ Mid Point A
Frequency < Base Frequency ≤ Mid Point B
Frequency ≤ Maximum Output Frequency]
Causes
These parameters are set at the same time:
• C6-05 > 6 [Carrier Freq Proportional Gain > 6]
• C6-04 > C6-03 [Carrier Frequency Lower Limit
> Carrier Frequency Upper Limit]
Note:
When C6-05 < 7, C6-04 becomes disabled. C6-
03 stays active.
C6-02 to C6-05 settings are not in the applicable
setting range.
Causes
This version of bypass software is not compatible
with the connected drive.
Causes
These parameters are set at the same time:
• b8-01 = 1 [Energy Saving Control Selection =
Enabled]
• S1-01 = 1 [Dynamic Noise Control = Enabled]
Causes
The baud rate setting [H5-02] does not align with the
currently selected protocol [H5-08].
One of these contradictory settings is true:
• H5-08 = 1 and H5-02 ≠3 [Communication
Protocol Selection = Metasys/N2 and
Communication Speed Selection ≠ 9600 bps]
• H5-08 = 2 and H5-02 ≠ 2, 3 [Communication
Protocol Selection = Apogee/P1 and
Communication Speed Selection ≠ 4800 bps, 9600
bps]
• H5-08 = 3 and H5-02 ≠ 3, 4, 5, 7 [Communication
Protocol Selection = BACnet and Communication
Speed Selection ≠ 9600 bps, 19.2 kbps, 38.4 kbps,
76.8 kbps]
Causes
These two parameters are set at the same time:
• H2-60 ≠ F [Term M1-M2 Secondary Function ≠
Not Used]
• H2-01 = 1xx [Term M1-M2 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
• H2-63 ≠ F [Term M3-M4 Secondary Function ≠
Not Used]
• H2-02 = 1xx [Term M3-M4 Function Selection =
Inverse output of xx]
These two parameters are set at the same time:
• H2-66 ≠ F [Term M5-M6 Secondary Function ≠
Not Used]
• H2-03 = 1xx [Term M5-M6 Function Selection =
Inverse output of xx]
6.7 Parameter Setting Errors
Possible Solutions
Set the parameters correctly to satisfy the conditions.
Possible Solutions
Set C6-02 to C6-05 correctly.
Possible Solutions
Flash the drive with compatible software.
Possible Solutions
Disable Energy Saving Control or Dynamic Noise Control.
Possible Solutions
Correct the parameter settings.
Possible Solutions
Clear the H2-01 to H2-03 = 1xx [Inverse output of xx] settings.
Note:
It is not possible to set H2-01 to H2-03 = 1xx [Inverse output of
xx] when using output functions for logic operations (H2-60,
H2-63, H2-66 ≠ F).