YASKAWA HV600 Technical Reference page 271

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

51: Sequence Timer Disable
Setting Value
Function
51
Sequence Timer Disable
ON : Sequence Timer is Disabled
The drive ignores Sequence Timers and operates as usual as specified by b1-02 [Run Command Selection 1].
52: Sequence Timer Cancel
Setting Value
Function
52
Sequence Timer Cancel
ON : Cancel Active Sequence Timer
Operation will continue with the next scheduled sequence timer. When you cancel the sequence timer before you
cycle the Run command, it will enable the sequence timer again.
61: Speed Search from Fmax
Setting Value
Function
61
Speed Search from Fmax
When the terminal is turned ON for b3-24 = 2 [Speed Search Method Selection = Current Detection 2], the drive
starts speed search from the maximum output frequency.
Note:
• The drive will detect oPE03 [Multi-Function Input Setting Err] when H1-xx = 61 and 62 are set at the same time.
• Refer to "b3: Speed Search" for more information.
62: Speed Search from Fref
Setting Value
Function
62
Speed Search from Fref
When the terminal is turned ON for b3-24 = 2 [Speed Search Method Selection = Current Detection 2], the drive
starts speed search from the frequency reference.
Note:
• The drive will detect oPE03 [Multi-Function Input Setting Err] when H1-xx = 61 and 62 are set at the same time.
• Refer to "b3: Speed Search" for more information.
63: Field Weakening
Setting Value
Function
63
Field Weakening
Note:
Refer to
d6: Field Weakening on page 241
68: High Slip Braking (HSB) Activate
Setting Value
Function
68
High Slip Braking (HSB)
Activate
Note:
• When you restart the drive after you use high-slip braking, make sure that the drive fully stops the motor then clear the high-slip braking
input.
• Refer to "n3: High Slip/Overex Braking" for more information.
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Sets the command to disable Sequence Timers.
Sets the command to cancel the currently active Sequence Timer.
Sets the function to start speed search using an external reference although b3-01 = 0 [Speed Search Selection at Start = Disabled].
Sets the function to use an external reference to start speed search although b3-01 = 0 [Speed Search Selection at Start = Disabled].
Sets the function to send the Field Weakening Level and Field Weakening Frequency Limit commands set in d6-01 [Field
Weakening Level] and d6-02 [Field Weakening Frequency Limit] when the input terminal is activated.
for more information.
Sets the command to use high-slip braking to stop the motor.
5.7 H: Terminal Functions
Description
Description
Description
Description
Description
Description
5
271