H6: Pulse Train Input/Output; H7: Virtual Mfio Selection - YASKAWA GA500 GA50U Series Programming Manual

Table of Contents

Advertisement

H6: Pulse Train Input/Output

No.
Name
(Hex.)
H6-01
Terminal RP Pulse Train
Function
(042C)
H6-02
Terminal RP Frequency
Scaling
(042D)
RUN
H6-03
Terminal RP Function Gain
(042E)
RUN
H6-04
Terminal RP Function Bias
(042F)
RUN
H6-05
Terminal RP Filter Time
(0430)
RUN
H6-06
Terminal MP Monitor
Selection
(0431)
RUN
H6-07
Terminal MP Frequency
Scaling
(0432)
RUN
H6-08
Terminal RP Minimum
Frequency
(043F)

H7: Virtual MFIO Selection

No.
Name
(Hex.)
H7-00
Virtual MFIO selection
(116F)
Expert
H7-01
Virtual Multi-Function Input
1
(1185)
Expert
H7-02
Virtual Multi-Function Input
2
(1186)
Expert
H7-03
Virtual Multi-Function Input
3
(1187)
Expert
H7-04
Virtual Multi-Function Input
4
(1188)
Expert
H7-10
Virtual Multi-Function
Output 1
(11A4)
Expert
YASKAWA TOEPYAIGA5002A GA500 DRIVE PROGRAMMING
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function for pulse train input terminal RP.
0 : Frequency Reference
1 : PID Feedback Value
2 : PID Setpoint Value
3 : Speed Feedback (V/F Control)
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency of the pulse train input signal used when the item selected with H6-01 [Terminal
RP Pulse Train Function] is input at 100%.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the gain used when the function in H6-01 [Terminal RP Pulse Train Function] is input to
terminal RP.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the bias used when the function in H6-01 [Terminal RP Pulse Train Function] is input to
terminal RP. Sets a value at the time when the pulse train is 0 Hz.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the time constant for the pulse train input primary delay filters.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets a function for pulse train monitor output terminal MP. Sets the "x-xx" part of the Ux-xx monitor.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the frequency of the pulse train output signal used when the monitor set with H6-06 [Terminal
MP Monitor Selection] is 100%.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the minimum frequency of the pulse train signal that terminal RP can detect.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function to enable and disable the virtual I/O function. Set this parameter to 1 to operate the
virtual I/O function.
0 : Disabled
1 : Enabled
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function that enters the virtual input set in H7-10 [Virtual Multi-Function Output 1].
Note:
1B [Programming Lockout] and 11B [Inverse Input of 1B] are not available.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function that enters the virtual input set in H7-12 [Virtual Multi-Function Output 2].
Note:
1B [Programming Lockout] and 11B [Inverse Input of 1B] are not available.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM EZOLV
Sets the function that enters the virtual input set in H7-14 [Virtual Multi-Function Output 3].
Note:
1B [Programming Lockout] and 11B [Inverse Input of 1B] are not available.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function that enters the virtual input set in H7-16 [Virtual Multi-Function Output 4].
Note:
1B [Programming Lockout] and 11B [Inverse Input of 1B] are not available.
V/f
OLV
OLV/PM AOLV/PM EZOLV
OLV/PM
Sets the function for virtual digital output 1.
Description
Description
1.10 H: Terminal Functions
Default
(Range)
0
(0 - 3)
1440 Hz
(100 - 32000 Hz)
100.0%
(0.0 - 1000.0%)
0.0%
(-100.0 - 100.0%)
0.10 s
(0.00 - 2.00 s)
102
(000, 031, 101, 102, 105,
116, 501, 502, 801 - 809,
821 - 825, 831 - 839, 851 -
855)
1440 Hz
(0 - 32000 Hz)
0.5 Hz
(0.1 - 1000.0 Hz)
Default
(Range)
0
(0, 1)
F
(1 - 19F)
F
(1 - 19F)
F
(1 - 19F)
F
(1 - 19F)
F
(0 - 1A7)
1
79

Advertisement

Table of Contents
loading

Table of Contents