YASKAWA HV600 Technical Reference page 95

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Type
Terminal
TB2-1
Digital Input 1
DI-1
(Run (AUTO))
TB2-2
Digital Input 2
DI-2
(Run Enable - Safety (NC))
TB2-3
Digital Input 3
DI-3
(Run Interlock (BAS))
TB2-4
Digital Input 4
DI-4
(Remote Transfer to Bypass)
TB2-5
Digital Input 5
Digital Inputs
DI-5
(Emergency Override Bypass)
TB2-6
Digital Input 6
DI-6
(-)
TB2-7
Digital Input 7
DI-7
(-)
TB2-8
Digital Input 8
DI-8
(-)
TB2-9/10
Isolated Ground
IG24
Type
Terminal
TB4-1
Analog Input Power Supply
+10 Vdc
TB4-2
Analog Input
Analog Input Speed Reference
AI
TB4-3
Analog Input Common
COMMON
Bypass Control Circuit Terminal Block Output Functions
Type
Terminal
TB1-1/2/3
Digital Output 7
DO-7
(Motor Run)
TB1-4/5/6
Digital Output 8
DO-8
(HAND Mode)
Digital Outputs
TB1-7/8/9
Digital Output 9
DO-9
(AUTO Mode)
TB1-10/11/
Digital Output 10
12
(System Fault)
DO-10
Type
Terminal
TB6-1/2
Ground
Chassis Ground
GROUND
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Table 3.14 Bypass Digital Input Terminals (TB2)
Name (Default)
Dry contact rated, photocoupler sinking input to IG24, 24 Vdc 8 mA,
Ground fault protected
Digital input common
Table 3.15 Bypass Analog Input Terminals (TB4)
Name (Default)
AUTO Mode
Speed Reference
0 to 10 Vdc (20 kΩ) or 4 to 20 mA (250 Ω)
Table 3.16 Bypass Digital Output Terminals (TB1)
Name (Default)
Relay, dry contact form C, 30 Vdc or 120 Vac,
DO-7 to DO-10 for customer use, 2 Amp
Table 3.17 Control Circuit Ground Terminals (TB6)
Name (Default)
-
3.5 Bypass PCB Control Circuit
Function (Signal Level)
Function (Signal Level)
Function (Signal Level)
Function (Signal Level)
3
95

Advertisement

Table of Contents
loading

Table of Contents