H4-03: Terminal FM Analog Output Bias
No.
Name
(Hex.)
H4-03
Terminal FM Analog Output
Bias
(041F)
RUN
The analog signal output from the FM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with H4-
07 [Terminal FM Signal Level Select].
H4-04: Terminal AM Analog Output Select
No.
Name
(Hex.)
H4-04
Terminal AM Analog Output
Select
(0420)
Set the x-xx part of the Ux-xx [Monitor]. For example, set H4-04 = 103 to monitor U1-03 [Output Current].
Note:
When you use the terminal in through mode, set this parameter to 000 or 031. You can set the terminal AM output level from the PLC
through MEMOBUS/Modbus communications or the communication option.
H4-05: Terminal AM Analog Output Gain
No.
Name
(Hex.)
H4-05
Terminal AM Analog Output
Gain
(0421)
RUN
The analog signal output from the AM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with H4-
08 [Terminal AM Signal Level Select].
Example settings:
When the output current of a monitoring item is 100% (drive rated current) in these examples, the voltage of AM
terminal outputs at 5 V (50% of 10 V). Subsequently, the output current at the time the AM terminal outputs a
maximum voltage of 10 V will be 200% of the drive rated current.
• H4-04 = 103 [Terminal AM Analog Output Select = Output Current]
• H4-05 = 50.0%
• H4-06 = 0.0% [Terminal AM Analog Output Bias = 0.0%]
• H4-08 = 0 [0 to 10 V]
H4-06: Terminal AM Analog Output Bias
No.
Name
(Hex.)
H4-06
Terminal AM Analog Output
Bias
(0422)
RUN
The analog signal output from the AM terminal is a maximum of ±10 V (or 20 mA). Select the signal level with H4-
08 [Terminal AM Signal Level Select].
H4-07: Terminal FM Signal Level Select
No.
Name
(Hex.)
H4-07
Terminal FM Signal Level
Select
(0423)
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Sets the bias of the monitor signal that is sent from MFAO terminal FM.
Sets the monitoring number to be output from the MFAO terminal AM.
Sets the gain of the monitor signal that is sent from MFAO terminal AM.
Sets the bias of the monitor signal that is sent from MFAO terminal AM.
Sets the MFAO terminal FM output signal level.
Description
Description
Description
Description
Description
5.7 H: Terminal Functions
Default
(Range)
0.0%
(-999.9 - +999.9%)
Default
(Range)
103
(000 - 999)
Default
(Range)
50.0%
(-999.9 - +999.9%)
Default
(Range)
0.0%
(-999.9 - +999.9%)
Default
(Range)
0
(0, 2)
305
5