YASKAWA HV600 Technical Reference page 96

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

3.5 Bypass PCB Control Circuit
Bypass Serial Communication Terminals
Type
Terminal
TB3-1
IG5
TB3-2
TXRX+
Serial
Communication
TB3-3
TXRX-
TB3-4
SHIELD
Switches on the Bypass PCB
The bypass PCB has switches to adapt the bypass I/Os to the external control signals as shown in
Set the switches to select the functions for each terminal.
96
Table 3.18 Bypass Serial Communication Terminals (TB3)
Terminal Name
Ground reference for RS-485 signals. This is an isolated ground used only for communications and may be used in
Isolated ground
certain circumstances to connect the floating ground references of other communication devices.
• BACnet communications
(+) Differential
communication signal
• APOGEE FLN communications
• MEMOBUS/ Modbus communications
• Metasys N2 communications
Use an RS-485 cable to connect the drive.
(-) Differential
Note:
communication signal
Make sure that DIP switch S1 is ON to enable the
termination resistor in the last drive in a BACnet,
APOGEE FLN, MEMOBUS/ Modbus, or Metasys
N2 network.
Shield tie point
Capacitively coupled to chassis ground.
Figure 3.11 Locations of Switches
Function (Signal Level)
• RS-485
• BACnet communications: Maximum 76.8 kbps
• APOGEE FLN communications: 4.8 or 9.6 kbps
• MEMOBUS/Modbus communications: Maximum
115.2 kbps
• Metasys N2 communications: 9.6 kbps
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference