5.2

b: Application

b parameters set these functions:
• Frequency reference source/Run command source
• Stopping method settings
• DC Injection Braking
• Speed Search
• Timer Function
• PID control
• Energy Savings Control

b1: Operation Mode Selection

b1 parameters set the operation mode for the drive.
b1-01: Frequency Reference Selection 1
No.
Name
(Hex.)
b1-01
Frequency Reference
Selection 1
(0180)
Note:
• Push
on the keypad to set the input mode to HAND and enter the frequency reference from the keypad.
• When the drive receives a Run command when the frequency reference is 0 Hz or less than the E1-09 [Minimum Output Frequency] value,
on the keypad will flash. Examine the setting for the frequency reference input and enter a value ≥ E1-09.
0 : Keypad
The bypass uses the keypad to enter the frequency reference and also switches the PID setpoint to YA-01 [Setpoint 1].
Use
and
on the keypad to change the frequency reference.
1 : Analog Input
The bypass uses MFAI on the bypass board to input an analog frequency reference with a voltage or current input
signal.
• Voltage Input
Refer to
Table 5.18
to use a voltage signal input to one of the MFAI terminals.
Terminal
Terminal Signal Level
Bypass MFAI
0 - 10 V
Figure 5.1 Example of Setting the Frequency Reference with a Voltage Signal to the Bypass MFAI
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Sets the input method for the frequency reference.
Table 5.18 Frequency Reference Voltage Input
Parameter Settings
Signal Level Selection
Z2-30 = 0
Description
Gain
Bias
Z2-32
Z2-33
5.2 b: Application
Default
(Range)
1
(0 - 3)
Note
Set Jumper Switch S2 to "V" for
voltage input.
187