6.6 Minor Faults/Alarms
Code
Name
FREEZ_ST
Freeze Stat Open
Code
Name
FR<MS
Freq Ref < Minimum Speed (Y1-06)
Note:
• If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
• If the drive detects this error, it internally sets the frequency reference to the value set in Y1-06.
Code
Name
FR<TH
Freq. Reference < Thrust (Y4-12)
Note:
• If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
• If the drive detects this error, it internally sets the frequency reference to the value set in Y4-12.
Code
Name
HCA
High Current Alarm
Note:
• The drive detects this error if the drive output current is more than the overcurrent alarm level (150% of the rated current).
• If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code
Name
HIAUX
High PI Aux Feedback Level
Note:
If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
Code
Name
HIFB
High Feedback Sensed
Note:
• If the drive detects this error, the terminal set to H2-01 to H2-03 = 10 [MFDO Function Selection = Alarm] will activate.
• If the drive detects this error, it will respond as specified by the setting of Y1-13 [High Feedback Selection].
502
Causes
The bypass detected a Freeze Stat condition.
Causes
The drive frequency reference setting is less than the
value set in Y1-06 [Minimum Speed] in these
conditions:
• The drive is not in PI Mode
• The drive is running
• Minimum Speed is enabled (Y1-06 > 0.00)
• Y1-06 > Y4-12 [Thrust Frequency]
Causes
The drive frequency reference setting is less than the
value set in Y4-12 [Thrust Frequency] in these
conditions:
• The drive is not in PI Mode
• The drive is running
• Thrust is enabled (Y4-11 [Thrust Acceleration
Time] > 0.00 and Y4-12 > Y1-06 [Minimum
Speed])
Causes
The load is too heavy.
The acceleration time is too short.
The drive is trying to operate a specialized motor or a
motor that is larger than the maximum applicable
motor output of the drive.
The current level temporarily increased because of
speed search after a momentary power loss or while
trying to Auto Restart.
Causes
PI Auxiliary Feedback is more than the level set in
YF-12 [PI Aux Control High Level Detect] for the
time set in YF-13 [PI Aux High Level Detection Time]
in these conditions:
• The drive operates in AUTO Mode.
• The output frequency > 0.
Causes
The feedback level is more than the level set in Y1-11
[High Feedback Level].
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Possible Solutions
• Check the digital input programmed for Freeze Stat Switch (Z2-
0x = 39).
• Check the connected device for continuity.
• Check Bypass Digital Input Invert Settings in Z2-09 to Z2-16.
Possible Solutions
Increase the frequency reference to a value more than Y1-06.
Possible Solutions
Increase the frequency reference to a value more than Y4-12.
Possible Solutions
• Decrease the load for applications with repetitive starts and
stops.
• Replace the drive with a larger capacity model.
• Calculate the torque necessary during acceleration related to the
load inertia and the specified acceleration time.
• Increase the values set in C1-01 or C1-03 [Acceleration Times]
until you get the necessary torque.
• Increase the values set in C2-01 to C2-04 [S-Curve
Characteristics] until you get the necessary torque.
• Replace the drive with a larger capacity model.
• Examine the motor nameplate, the motor, and the drive to make
sure that the drive rated current is larger than the motor rated
current.
• Replace the drive with a larger capacity model.
If speed search or Auto Restart cause an increase in current, the
drive can temporarily show this alarm. The time that the drive
shows the alarm is short. No more steps are necessary to clear the
alarm.
Possible Solutions
• Decrease the PI Auxiliary Feedback level to less than YF-12.
• Set YF-12 and YF-13 correctly.
Possible Solutions
• Decrease the feedback level to less than Y1-11 - Y1-14
[Hysteresis Level].
• Set Y1-11 and Y1-12 correctly.