YASKAWA HV600 Technical Reference page 178

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

5.1 A: Initialization Parameters
Note:
• Before you set A1-06, make sure that you set A1-03 = 2220 [Initialize Parameters = 2-Wire Initialization] to initialize parameters.
• It is not possible to change the A1-06 value. To set an application preset, first set A1-03 = 2220 to initialize parameters, then set this
parameter. If initializing all parameters will cause a problem, do not change the settings.
If you set A2-33 = 1 [User Parameter Auto Selection = Enabled: Auto Save Recent Parms] to set parameters to A2-17 to A2-32 [User
Parameters 17 to 32] automatically, the drive will reset these parameters when you change the A1-06 setting.
0 : No Preset Selected
The drive saves the parameters in
Table 5.3 Parameters Saved as User Parameters with the No Preset Selected
User Parameter No.
A2-01
A2-02
A2-03
A2-04
A2-05
A2-06
A2-07
A2-08
A2-09
A2-10
A2-11
A2-12
A2-13
A2-14
A2-15
A2-16
A2-17
A2-18
A2-19
A2-20
A2-21
A2-22
A2-23
A2-24
A2-25
1 : General Purpose Fan
The drive automatically sets the parameters in
Table 5.4 Best Parameter Settings for General Purpose Fan Applications
No.
A1-02
b1-03
b1-04
C1-01
L5-01
The drive saves the parameters in
178
Table 5.3
as user parameters.
Parameter No. Saved
b1-01
b1-02
b1-03
C1-01
C1-02
C6-02
d1-01
d1-02
d1-03
d1-04
d1-17
E1-01
E1-03
E1-04
E1-05
E1-06
E1-09
E1-13
E2-01
E2-04
E2-11
H4-02
L1-01
L3-04
Table 5.4
for a general purpose fan application.
Name
Control Method Selection
Stopping Method Selection
Reverse Operation Selection
Acceleration Time 1
Number of Auto-Restart Attempts
Table 5.5
as user parameters.
-
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Name
Frequency Reference Selection 1
Run Command Selection 1
Stopping Method Selection
Acceleration Time 1
Deceleration Time 1
Carrier Frequency Selection
Reference 1
Reference 2
Reference 3
Reference 4
Jog Reference
Input AC Supply Voltage
V/f Pattern Selection
Maximum Output Frequency
Maximum Output Voltage
Base Frequency
Minimum Output Frequency
Base Voltage
Motor Rated Current (FLA)
Motor Pole Count
Motor Rated Power
Terminal FM Analog Output Gain
Motor Overload (oL1) Protection
Stall Prevention during Decel
-
Optimal Value
0: V/f Control
1: Coast to Stop
1: Reverse Disabled
60.0 s
10