3.3 Main Circuit Wiring
Model
H6BP
Current Rating
Amps
D088
150
D114
175
D143
250
D169
250
D211
400
D273
400
Motor Wiring
Standard Motor
Terminal Block TB1
Model
H6BP
Tightening
AWG,
Torque
kcmil
(in lb)
D002
14-2
32
D003
14-2
32
D004
14-2
32
D007
14-2
32
D010
14-2
32
D016
14-2
32
D024
14-2
32
D030
14-2
32
D046
14-2
32
D059
14-2
32
D074
6-2/0
120
D088
14 - 8 or 6 -
50 or 120
2/0
D114
14 - 10 or 8
35 or 40 or
or 6 - 2/0
120
D143
6 - 350
275
kcmil
D169
6 - 350
275
kcmil
D211
(1-2) x (4 -
(1-2) x 500
500 kcmil)
D273
(1-2) x (4 -
(1-2) x 500
500 kcmil)
*1
24-16 is acceptable for solid wire or ferrule use only.
84
Standard Non-Fused
Input Disconnect Switch S1
AWG, kcmil
14 - 10 or 8 - 3/0
4 - 4/0
3/0-350 kcmil
3/0-350 kcmil
(1-2) x (2/0-500 kcmil)
(1-2) x (2/0-500 kcmil)
Table 3.6 Output and Control Wiring
Ground Wiring
Terminal Blocks
Tightening
TB1, TB3-TB6
AWG,
Torque
kcmil
(in lb)
AWG,
kcmil
14-10, 8, 6-
35, 40, 45,
24-16
4, or 2
or 50
14-10, 8, 6-
35, 40, 45,
24-16
4, or 2
or 50
14-10, 8, 6-
35, 40, 45,
24-16
4, or 2
or 50
14-10, 8, 6-
35, 40, 45,
24-16
4, or 2
or 50
14-10, 8, 6-
35, 40, 45,
24-16
4, or 2
or 50
14-10, 8, 6-
35, 40, 45,
24-16
4, or 2
or 50
14-10, 8, 6-
35, 40, 45,
24-16
4, or 2
or 50
14-10, 8, 6-
35, 40, 45,
24-16
4, or 2
or 50
14-10, 8, 6-
35, 40, 45,
24-16
4, or 2-1/0
or 50
14-10, 8, 6-
35, 40, 45,
24-16
4, or 2-1/0
or 50
14-10, 8, 6-
35, 40, 45,
24-16
4, or 2-1/0
or 50
14-10, 8, 6-
35, 40, 45,
24 - 16
4, or 2
or 50
14-10, 8, 6-
35, 40, 45,
24 - 16
4, or 2
or 50
14-10, 8, 6-
35, 40, 45,
24 - 16
4, or 2
or 50
14-10, 8, 6-
35, 40, 45,
24 - 16
4, or 2
or 50
14 - 2/0
120
24 - 16
14 - 2/0
120
24 - 16
Tightening Torque
Current Rating
(in lb)
Amps
50 or 120
150
225
150
225
250
225
250
(1-2) x 442
400
(1-2) x 442
600
A1
A1
Terminal Block
TB2 (FE)
Tightening
Tightening
AWG,
Torque
Torque
kcmil
(in lb)
(in lb)
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
8.85 to
*1
4.4 to 5.3
24-18
10.62
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
With Option PM
Circuit Breaker CB1
AWG, kcmil
14 - 10 or 8 - 3/0
14 - 10 or 8 - 3/0
3/0 - 350 kcmil
3/0 - 350 kcmil
(1-2) x (2/0-500 kcmil)
(1-2) x (2/0-500 kcmil)
Control Wiring
A2
Terminal Blocks
TB1-TB4 and TB6
Tightening
AWG,
Torque
kcmil
(in lb)
26-14
4
26-14
4
26-14
4
26-14
4
26-14
4
26-14
4
26-14
4
26-14
4
26-14
4
26-14
4
26-14
4
26 - 14
4
26 - 14
4
26 - 14
4
26 - 14
4
26 - 14
4
26 - 14
4
Tightening Torque
(in lb)
50 or 120
50 or 120
225
225
(1-2) x 442
(1-2) x 442
Panel
Terminal Block
TB4
Tightening
AWG,
Torque
kcmil
(in lb)
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1
26-10
5.3 to 7.1