5.7 H: Terminal Functions
Note:
All analog input scaling uses gain and bias for adjustment. Set the gain and bias values correctly.
Example Analog
Setting of Terminal A1
Input Settings
Frequency
• H3-02 = 0 [Terminal A1 Function
reference with the
Selection = Frequency Reference]
gain setting
• H3-03: 200.0 [Terminal A1 Gain
adjusted
Setting = 200%]
• H3-04 = 0.0 [Terminal A1 Bias
Setting = 0.0%]
• H3-02 = 0 [Frequency Reference]
Frequency
reference with the
• H3-03 = 100.0 [100.0%]
negative number
• H3-04 = -25.0 [-25.0%]
bias set
MEMOBUS/Modbus MFAI 1 to MFAI 3 Function Selection
Set the MFAI function to MEMOBUS/Modbus register 15C1 to 15C3 (Hex.) [MEMOBUS MFAI 1 to MFAI 3
Command]. Use H3-40 to H3-42 [Mbus Reg 15C1h to 15C3h Input Function] to set the function and use H3-43
[Mbus Reg Inputs FilterTime Const] to set the input filter.
Register No.
(Hex.)
15C1
15C2
15C3
*1
Set as 100% = 4096.
294
• When you input a 10 V signal, the frequency reference will be 200%.
• When you input a 5 V signal, the frequency reference will be 100%.
When you input a 5 V or more signal, E1-04 [Maximum Output Frequency] will limit the drive output and the
frequency reference will be 100%.
• When you input a 0 V signal, the frequency reference will be -25%.
• When you input a 0 V to 2 V signal, the frequency reference will be 0%.
• When you input a 2 V to 10 V signal, the frequency reference will be 0% to 100%.
Table 5.44 MEMOBUS Multi-Function AI Command Register
Name
MEMOBUS MFAI 1 Command
MEMOBUS MFAI 2 Command
MEMOBUS MFAI 3 Command
Figure 5.58 Functional Block Diagram for MEMOBUS MFAI Command 1
Frequency Reference
Range
*1
-32767 to 32767
-32767 to 32767
-32767 to 32767
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference