YASKAWA HV600 Technical Reference page 239

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Note:
• When you set Jump Frequencies 1 to 3, make sure that the parameters do not overlap.
• When the drive is in the range of the Jump frequency, the frequency reference changes automatically. When Jump is executed, the output
frequency changes smoothly as specified by the values set in C1-01 [Acceleration Time 1] and C1-02 [Deceleration Time 1].
d3-01: Jump Frequency 1
No.
Name
(Hex.)
d3-01
Jump Frequency 1
(0294)
Note:
Set this parameter to 0.0 Hz to disable the Jump frequency.
d3-02: Jump Frequency 2
No.
Name
(Hex.)
d3-02
Jump Frequency 2
(0295)
Note:
Set this parameter to 0.0 Hz to disable the Jump frequency.
d3-03: Jump Frequency 3
No.
Name
(Hex.)
d3-03
Jump Frequency 3
(0296)
Note:
Set this parameter to 0.0 Hz to disable the Jump frequency.
d3-04: Jump Frequency Width
No.
Name
(Hex.)
d3-04
Jump Frequency Width
(0297)
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Figure 5.35 Jump Frequency
Sets the median value of the frequency band that the drive will avoid.
Sets the median value of the frequency band that the drive will avoid.
Sets the median value of the frequency band that the drive will avoid.
Sets the width of the frequency band that the drive will avoid.
Description
Description
Description
Description
5.4 d: References
Default
(Range)
0.0 Hz
(0.0 - 400.0 Hz)
Default
(Range)
0.0 Hz
(0.0 - 400.0 Hz)
5
Default
(Range)
0.0 Hz
(0.0 - 400.0 Hz)
Default
(Range)
1.0 Hz
(0.0 - 20.0 Hz)
239