YASKAWA HV600 Technical Reference page 447

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

41: OverPressure Switch (NC)
Setting Value
Function
41
OverPressure Switch (NC)
42: Low Suction Switch (NC)
Setting Value
Function
42
Low Suction Switch (NC)
43: Vibration Switch (NC)
Setting Value
Function
43
Vibration Switch (NC)
44: Emergency Override Drive (REV)
Setting Value
Function
44
Emergency Override Drive
(REV)
The preset speed is equal to Z1-10.
45: Serial Hardware Test (RS-485)
Setting Value
Function
45
Serial Hardware Test (RS-
485)
46: Low City Pressure
Setting Value
Function
46
Low City Pressure
47: Motor Preheat
Setting Value
Function
47
Motor Preheat
Z2-23 to Z2-26 Digital Output 7 to 10 Function Selection
The drive has 4 digital output terminals. Refer to
No.
Z2-23
Digital Output 7 (TB1 1~3)
Z2-24
Digital Output 8 (TB1 4~6)
Z2-25
Digital Output 9 (TB1 7~9)
Z2-26
Digital Output 10 (TB1 10~12)
Setting Value
0
Serial Communication Control
1
K1 Drive Input Contactor
2
K2 Drive Input Contactor
3
K3 Bypass Contactor
4
K4 Motor 1 Contactor
5
K5 Motor 2 Contactor
6
READY
7
RUN Active
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Stops the drive from running and shows "OverPressure" on the keypad.
Stops the drive from running and shows "Low Suction" on the keypad.
Stops the drive from running and shows "Vibration" on the keypad.
The bypass controller stays in this state even if the drive faults or is unavailable.
Indicates that sufficient or insufficient pressure is present on the inlet to the pump. Used mainly for pressure booster situations.
Sets the command to apply the motor pre-heat current.
Table 5.72
Table 5.72 Digital Output Default Settings and Functions
Name
Table 5.73 Digital Output Setting Values
Function
Reference
448
448
448
448
449
449
449
449
Description
Description
Description
Description
Description
Description
Description
for default settings and functions.
Default
7
RUN Active
10
HAND mode Active
12
Auto mode Active
15
Fault Active
Setting Value
Function
8
Drive RUN active
9
Bypass RUN active
10
HAND mode Active
11
OFF mode Active
12
Auto mode Active
13
Drive Mode Selected
14
Bypass Mode Selected
15
Fault Active
5.14 Z: Bypass Parameters
Function
Reference
449
449
449
449
449
450
450
450
5