Installation Positions And Clearances; Narrow Bypass Installation Position And Clearances - YASKAWA HV600 Technical Reference

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

2.3

Installation Positions and Clearances

Narrow Bypass Installation Position and Clearances

Installation Dimensions
Refer to the Dimension Drawing (DD.HB.x.xx.xx) packaged with the bypass for exterior and mounting dimensions
for your model.
Installation Position
Install the bypass vertically for sufficient cooling airflow.
A - Vertical installation
Single Narrow Bypass Installation Clearances
Use the clearances specified in
airflow.
A - 50 mm (2 in) minimum
B - 30 mm (1.2 in) minimum
*1
This is the distance from a component or mounting bracket that has the maximum height. The highest component is different for different
models.
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Figure 2.1 Installation Position
Figure 2.2
to install the bypass. Make sure that there is sufficient space for wiring and
Figure 2.2 Single Bypass Installation
2.3 Installation Positions and Clearances
B - Horizontal installation
C - 120 mm (4.7 in) minimum
D - Airflow direction
*1
2
35