YASKAWA HV600 Technical Reference page 705

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Object Name
Object ID
(Network Display, if
Different)
Fault Details
• bit 0: oC
[Overcurrent], GF
[Ground Fault]
• bit 1: ov
[Overvoltage]
• bit 2: oL2 [Drive
Overload]
• bit 3: oH1 [Heatsink
Overheat], oH2
[External Overheat
(H1-XX=B)]
• bit 4 to 6: Reserved
• bit 7: EF to EF7
[External Fault]
• bit 8: CPFxx
[Hardware Fault]
(includes oFAxx)
• bit 9: oL1 [Motor
Overload], oL3
[Overtorque
AV7
Detection 1], UL3
[Undertorque
Detection 1]
• bit A: Reserved
• bit B: Uv [DC Bus
Undervoltage]
• bit C: Uv1[DC Bus
Undervoltage], Uv2
[Control Power
Undervoltage], Uv3
[Soft Charge
Answerback Fault]
• bit D: LF [Output
Phase Loss], PF
[Input Phase Loss]
• bit E: CE [Modbus
Communication
Error], bUS [Option
Communication
Error]
• bit F: oPr [Keypad
Connection Fault]
Data Link Status
• bit 0: Writing Data
• bit 1: Reserved
• bit 2: Reserved
• bit 3: Upper or lower
AV8
limit error
• bit 4: Data
conformity error
• bit 5: Writing to
EEPROM
• bit 6 to F: Reserved
AV9
Frequency Reference
AV10
Output Frequency
AV11
Output Voltage
AV12
Output Current
AV13
Output Power
AV14
Torque Reference
Drive Multi-Function
Input Status
AV15
(MF Input Status)
AV16
Drive Status 2
Drive Multi-Function
Output Status
AV17
(MF Output Status)
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Modbus Reg.
Precision
0021h
-
0022h
-
XXX.XX
0040h
Determined by o1-03
XXX.XX
0041h
Determined by o1-03
0045h
XXXX.X
0026h
XXXX.X
XXXX.X > 11kVA
0047h
XXX.XX <= 11kVA
0048h
XXXX.X
002Bh
XXX
002Ch
XXXXX
002Dh
XXX
10.3 BACnet Communications
Range
Units
0-65535
Bitmap
0-63
Bitmap
0-600.00
Determined by o1-03
0-600.00
Determined by o1-03
0-6553.5
V
0-6553.5
A
0-6553.5 > 11kVA
KW
0-655.35 <= 11kVA
0-100.0
%
0-127
Bitmap
0-65535
Bitmap
0-135
Bitmap
PV Access
R
R
R
R
R
R
R
R
10
R
R
R
705