5.10 o: Keypad-Related Settings
o1-15: Freq. Reference Custom Unit 3
No.
Name
(Hex.)
o1-15
Freq. Reference Custom
Unit 3
(3107)
Refer to
Custom Units on page 213
o1-18: User Defined Parameter 1
No.
Name
(Hex.)
o1-18
User Defined Parameter 1
(310A)
o1-19: User Defined Parameter 2
No.
Name
(Hex.)
o1-19
User Defined Parameter 2
(310B)
o1-24 to o1-35: Custom Monitor 1 to 12
No.
Name
(Hex.)
o1-24 to o1-35
Custom Monitor 1 to 12
(11AD - 11B8)
RUN
These parameters save the monitor items selected by the HOA keypad [Custom Monitor].
Note:
• The default setting for o1-26 changes when b5-01 [PID Mode Setting] changes:
–b5-01 = 0 [Disabled]: 103
–b5-01 ≠ 0: 501
• You can show a maximum of three selected monitors on one HOA keypad screen.
–When you select only one monitor, the text size of this monitor increases. For example, when o1-25 to o1-35 = 0, the text size of the
monitor saved in o1-24 increases.
–When you select two monitors, the text size of these monitors increase.
–When you select four or more monitors, the fourth monitor and all additional monitors are shown on the next screens.
• Monitors selected with o1-24 to o1-26 can be displayed as a bar graph, analog gauge, or trend plot.
–Bar graph display: 3 monitors maximum
Select with o1-24, o1-25, and o1-26.
–Analog gauge display: 1 monitor
Select with o1-24.
–Trend plot display: 2 monitors
Select with o1-24 and o1-25.
• You can only set parameters o1-24 to o1-26 with analog output monitors.
• You can set all monitors to parameters o1-27 to o1-35.
o1-36: LCD Backlight Brightness
No.
Name
(Hex.)
o1-36
LCD Backlight Brightness
(11B9)
RUN
When you decrease the setting value, the intensity of the backlight decreases.
358
Sets the third character of the custom unit display when o1-03 = 3 [Frequency Display Unit Selection
= User Units] and o1-09 = 49 [Freq. Reference Display Units = Custom (o1-13~15)].
for more information about available selections.
Lets you set values to use as reference information.
Lets you set values to use as reference information.
Set a maximum of 12 monitors as user monitors. These parameters are only available on an HOA
keypad.
Sets the intensity of the HOA keypad backlight.
Description
Description
Description
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
(Range)
41
(20 - 7A)
Default
(Range)
0
(0 - 999)
Default
(Range)
0
(0 - 999)
Default
(Range)
o1-24: 101
o1-25: 102
o1-26: Determined by b5-01
o1-27 to o1-35: 0
(0, 101 - 1299)
Default
(Range)
5