9.14 S: Special Applications
No.
Name
(Hex.)
S2-05
Timer 1 Reference Source Selects the frequency reference source to run the drive when sequence timer 1 is active
(320A)
S2-06
Timer 2 Start Time
(320B)
S2-07
Timer 2 Stop Time
(320C)
S2-08
Timer 2 Day Selection
(320D)
S2-09
Timer 2 Sequence
Selection
(320E)
S2-10
Timer 2 Reference Source Selects the frequency reference source to run the drive when sequence timer 2 is active
(320F)
S2-11
Timer 3 Start Time
(3210)
648
(only applicable when S2-04 > 0 [Timer 1 Sequence Selection ≠ Digital Out Only]).
0 : Operator (d1-01/YA-01)
1 : Operator (d1-02/YA-02)
2 : Operator (d1-03/YA-03)
3 : Operator (d1-04/YA-04)
4 : Terminals
5 : Serial Com
6 : Option PCB
8 : Set by b1-01
Note:
For reference source 0 to 3, the drive will use d1-xx frequency reference when PID
mode is disabled and YA-xx setpoint when PID is enabled.
Sets the start time for timer 2.
Note:
• Default is when o4-22 = 1 [Time Format = 12 Hour Clock]. When o4-22 = 0 [24
Hour Clock], default is 00:00. When o4-22 = 2 [12 Hour JP Clock], default is 00:00
AM.
• Range is when o4-22 = 1. When o4-22 = 0, range is 00:00 to 24:00. When o4-22 =
2, range is 00:00 AM to 11:59 PM.
Sets the stop time for timer 2.
Note:
• Default is when o4-22 = 1 [Time Format = 12 Hour Clock]. When o4-22 = 0 [24
Hour Clock], default is 00:00. When o4-22 = 2 [12 Hour JP Clock], default is 00:00
AM.
• Range is when o4-22 = 1. When o4-22 = 0, range is 00:00 to 24:00. When o4-22 =
2, range is 00:00 AM to 11:59 PM.
Sets the days for which sequence timer 2 is active.
0 : Timer disabled
1 : Daily
2 : Mon - Fri
3 : Sat - Sun
4 : Monday
5 : Tuesday
6 : Wednesday
7 : Thursday
8 : Friday
9 : Saturday
10 : Sunday
Sets the drive response when sequence timer 2 is active.
0 : Digital Out Only
1 : Run
2 : Run - PID Disable
(only applicable when S2-09 > 0 [Timer 2 Sequence Selection ≠ 0]).
0 : Operator (d1-01/YA-01)
1 : Operator (d1-02/YA-02)
2 : Operator (d1-03/YA-03)
3 : Operator (d1-04/YA-04)
4 : Terminals
5 : Serial Com
6 : Option PCB
8 : Set by b1-01
Note:
For reference source 0 to 3, the drive will use d1-xx frequency reference when PID
mode is disabled and YA-xx setpoint when PID is enabled.
Sets the start time for timer 3.
Note:
• Default is when o4-22 = 1 [Time Format = 12 Hour Clock]. When o4-22 = 0 [24
Hour Clock], default is 00:00. When o4-22 = 2 [12 Hour JP Clock], default is 00:00
AM.
• Range is when o4-22 = 1. When o4-22 = 0, range is 00:00 to 24:00. When o4-22 =
2, range is 00:00 AM to 11:59 PM.
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
Ref.
(Range)
0
381
(0 - 8)
12:00
381
(12:00 AM - 11:59 PM)
12:00
381
(12:00 AM - 11:59 PM)
0
382
(0 - 10)
0
382
(0 - 2)
0
382
(0 - 8)
12:00
383
(12:00 AM - 11:59 PM)