Code
Name
HFB
High Feedback Sensed
Note:
• Do a Fault Reset to clear the fault.
• If the drive detects this fault, it will respond as specified by the setting of Y1-13 [High Feedback Selection].
• Parameter L5-41 [Hi Feedback Flt Retry Selection] sets the Auto Restart function of this fault.
Code
Name
HIAUX
High PI Aux Feedback Level
Note:
• Do a Fault Reset to clear the fault.
• Parameter YF-14 [PI Aux Hi Level Detection Select] sets the Auto Restart function of this fault.
Code
Name
HLCE
High Level Communication Errors
Note:
This fault occurs when the drive is a slave drive in Gateway Mode [F6-16 ≠ 0] and communication is lost from the master.
Code
Name
LF
Output Phase Loss
Note:
• The drive detects this fault if phase loss occurs on the output side of the drive.
• Do a Fault Reset to clear the fault.
• Set L8-07 [Output Phase Loss Protection Sel] to enable and disable LF detection.
Code
Name
LF2
Output Current Imbalance
Code
Name
LFB
Low Feedback Sensed
Note:
• Do a Fault Reset to clear the fault.
• If the drive detects this fault, it will respond as specified by the setting of Y1-10 [Low Feedback Selection].
• Parameter L5-40 [Low Feedback Flt Retry Selection] sets the Auto Restart function of this fault.
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Causes
The feedback level is more than the level set in Y1-11
[High Feedback Level] for the time set in Y1-12
[High Feedback Lvl Fault Dly Time].
Causes
PI Auxiliary Feedback is more than the level set in
YF-12 [PI Aux Control High Level Detect] for the
time set in YF-13 [PI Aux High Level Detection Time]
in these conditions:
• The drive operates in AUTO Mode.
• The output frequency > 0.
Causes
Communication data error occurred between the
option and the master drive when you use Gateway
function.
The master drive detects oFxxx and the slave drive
detects HLCE.
Causes
The motor main circuit cable is disconnected.
There is a disconnection in the motor coil winding.
The screws on the drive output terminals are loose.
The rated output current of the motor is less than 5%
of the drive rated current.
You are trying to use a single-phase motor.
The output transistor in the drive is damaged.
Causes
Phase loss occurred in the wiring on the output side
of the drive.
The output terminal screws of the drive are loose.
The drive output circuit is broken.
Causes
The feedback level is less than the level set in Y1-08
[Low Feedback Level] for the time set in Y1-09 [Low
Feedback Lvl Fault Dly Time].
Possible Solutions
• Decrease the feedback level less than Y1-11.
• Set Y1-11 and Y1-12 correctly.
Possible Solutions
• Decrease the PI Auxiliary Feedback level less than YF-12.
• Set YF-12 and YF-13 correctly.
Possible Solutions
Examine the wiring between the option and the master drive and
remove the cause of the fault.
Possible Solutions
Connect motor main circuit cable wiring. Correct wiring errors in
the main circuit drive input power.
If a coil is disconnected, measure the motor Line-to-Line Resistance
and replace the motor.
Tighten the terminal screws to the correct tightening torque.
Examine the drive capacity or the motor output to be applied.
The drive cannot operate a single-phase motor.
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
Examine for wiring errors or disconnected wires on the output side
of the drive, and repair problems.
Tighten the terminal screws to the correct tightening torque.
• Re-energize the drive.
• If the fault stays, replace the control board or the drive. For
information about replacing the control board, contact Yaskawa
or your nearest sales representative.
Possible Solutions
• Increase the feedback level to more than Y1-08.
• Set Y1-08 and Y1-09 correctly.