YASKAWA HV600 Technical Reference page 175

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Table 5.1
shows which keypad screens are available for each A1-01 settings.
Mode
Keypad Screen
Drive Mode
Monitors
Parameters
User Custom Parameters
Parameter Backup/
Restore
Modified Parameters/
Programming Mode
Fault Log
Auto-Tuning
Initial Setup Screen
Diagnostic Tools
Note:
• When you use A1-04 and A1-05 [Password Setting] to set a password, you cannot change these parameters:
–A1-01
–A1-03 [Initialize Parameters]
–A1-06 [Application Preset]
–A2-01 to A2-32
• When H1-xx = 1B [MFDI Function Selection = Program Lockout], you must activate the terminal to change parameter settings.
• When you use serial communications, you must send the Enter command from the controller to the drive and complete the serial
communication write process before you can use the keypad to change parameter settings.
A1-03: Initialize Parameters
No.
Name
(Hex.)
A1-03
Initialize Parameters
(0103)
Note:
• After you initialize the drive, the drive automatically sets A1-03 = 0.
• User Parameters can save the parameter values for your application and use these values as default values for drive initialization.
0 : No Initialization
1110 : User Initialization
Sets parameters to the values set by the user as user settings. Set o2-03 = 1 [User Parameter Default Value = Set
defaults] to save the user settings.
You can save the adjusted parameter settings from the test run as user-set default values to the drive. When you make
changes to the parameter values after you save the settings as User Parameter Settings, initialize with A1-03 = 1110
for the drive to set the parameters to the User Parameter Setting value.
Follow this procedure to save User Parameter setting values and to do a User Initialization:
1. Set parameters correctly for the application.
2. Set o2-03 = 1 [User Parameter Default Value = Set defaults].
This saves parameter settings for a User Initialization.
The drive will automatically set o2-03 = 0.
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Table 5.1 Access Level and Available Keypad Screens
0
1
Yes
Yes
Yes
Yes
No
Yes
No
No
No
No
No
No
No
No
No
No
Sets parameters to default values.
5.1 A: Initialization Parameters
A1-01 Setting
2
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Description
3
4
Yes
Yes
Yes
Yes
Yes
No
Yes
No
Yes
Yes
Yes
No
Yes
No
Yes
No
Default
(Range)
0
(0, 1110, 2220)
175
5