Type
Terminal
N.O. output
MA
(Fault)
N.C. output
Fault Relay
MB
Output
(Fault)
MC
Digital output common
M1
MFDO
(During Run)
M2
M3
MFDO
MFDO
(Zero Speed)
M4
M5
MFDO
(Speed Agree 1)
M6
Type
Terminal
MFAO 1
FM
(Output frequency)
MFAO 2
Monitor Output
AM
(Output current)
AC
Monitor common
External Power
+P
External power supply
Supply Output
Switches and Jumpers on the Drive Control PCB
The terminal board has switches to adapt the drive I/Os to the external control signals as shown in
Set the switches to select the functions for each terminal.
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Table 3.23 Control Circuit Output Terminals
Name (Default)
Drive Fault Signal Output
• Relay output
• 30 Vdc, 10 mA to 2 A
• 250 Vac, 10 mA to 2 A
• Minimum load: 5 V, 10 mA (Reference value)
Note:
This will signal drive-based faults only.
Multi Function Digital Output
• Relay output
• 30 Vdc, 10 mA to 2 A
• 250 Vac, 10 mA to 2 A
• Minimum load: 5 V, 10 mA (Reference value)
Note:
• These are active for drive-based conditions only.
• Do not set functions that frequently switch ON/OFF to MFDO (M1 to M6) because this will
decrease the performance life of the relay contacts. Yaskawa estimates switching life at
200,000 times (assumes 1 A, resistive load).
Table 3.24 Control Circuit Monitor Output Terminals
Name (Default)
Multi Function Analog Output
Select voltage or current output.
• 0 V to 10 V/0% to 100%
• 4 mA to 20 mA (receiver recommended impedance: 250 Ω)
Note:
• This functions in Drive Mode only.
• Select with jumper switch S5 and H4-07 [Terminal FM Signal Level Select] or H4-08
[Terminal AM Signal Level Select].
0 V
Power supply for external devices.
• 24 V (150 mA maximum)
3.6 Drive PCB Control Circuit
Function (Signal Level)
Function (Signal Level)
Figure
3.18.
3
103