9.15 T: Motor Tuning

9.15
T: Motor Tuning
T0: Tuning Mode Selection
No.
Name
(Hex.)
T0-00
Tuning Mode Selection
(1197)
T1: Induction Motor Auto-Tuning
No.
Name
(Hex.)
T1-01
Auto-Tuning Mode
Selection
(0701)
T1-02
Motor Rated Power
(0702)
T1-03
Motor Rated Voltage
(0703)
T1-04
Motor Rated Current
(0704)
T1-05
Motor Base Frequency
(0705)
T1-06
Number of Motor Poles
(0706)
T1-07
Motor Base Speed
(0707)
T1-11
Motor Iron Loss
(070B)
656
Sets the type of Auto-Tuning.
0 : Motor Parameter Tuning
Sets the type of Auto-Tuning.
0 : Rotational Auto-Tuning
2 : Stationary Line-Line Resistance
Uses the units set in o1-58 [Motor Power Unit Selection] to set the motor rated output
power.
Sets the rated voltage (V) of the motor. Enter the base speed voltage for constant output
motors.
Sets the rated current (A) of the motor.
Sets the base frequency (Hz) of the motor.
Sets the number of motor poles.
Sets the motor base speed for Auto-Tuning (min
Sets the iron loss for calculating the energy-saving coefficient.
Description
Description
-1
(r/min)).
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
Ref.
(Range)
0
405
(0)
Default
Ref.
(Range)
0
405
(0, 2)
Determined by o2-04
405
(0.00 - 650.00 HP)
Determined by o2-04
405
(208/240 V: 0.0 - 255.5 V,
480 V: 0.0 - 511.0 V)
Determined by o2-04
406
(10% to 200% of the
drive rated current)
60.0 Hz
406
(0.0 - 400.0 Hz)
4
406
(2 to 120)
1750 min
-1
(r/min)
406
-1
(0 - 24000 min
(r/min))
Determined by E2-11
406
(0 - 65535 W)

Advertisement