YASKAWA HV600 Technical Reference page 730

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

10.5 Metasys N2 Communications
Wiring Diagram for More than One Bypass
Figure 10.13
shows how to wire more than one connected bypass using serial communications.
Note:
When you install the bypass at the end of the network line, set DIP switch S1 to "ON" to enable the termination resistor. Set DIP switch S1 to
"OFF" on all other bypasses.
Bypass Operations by Serial Communications
Parameters will apply to the settings when the bypass is running during serial communications. This section gives
information about the available functions and their related parameters.
Executable Functions
A controller can do these operations with serial communications. Parameter settings (except H5-xx) do not have an
effect on the availability of these operations.
• Monitor the bypass status and operate the bypass
• Set and view parameters
• Fault Reset Procedure
730
Figure 10.12 Termination Resistor DIP Switch S1
R+
R-
PLC
S+
S-
IG
Figure 10.13 Wiring Diagram for More than One Bypass
Bypass
TXRX+
2
S1
3
TXRX-
1
IG5
OFF
Bypass
TXRX+
2
S1
3
TXRX-
1
IG5
OFF
Bypass
TXRX+
2
S1
3
TXRX-
1
IG5
ON
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference

Advertisement

Table of Contents
loading

Table of Contents