YASKAWA HV600 Technical Reference page 659

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

No.
Name
(Hex.)
Y2-03
Sleep Delay Time
(3C66)
RUN
Y2-04
Sleep Activation Level
(3C67)
RUN
Y2-05
Sleep Boost Level
(3C68)
RUN
Y2-06
Sleep Boost Hold Time
(3C69)
RUN
Y2-07
Sleep Boost Max Time
(3C6A)
RUN
Y2-08
Delta Feedback Drop
Level
(3C6B)
RUN
Y2-09
Feedback Drop Detection
Time
(3C6C)
RUN
Y2-23
Anti-No-Flow Bandwidth Sets the quantity of PI error bandwidth that the drive uses to detect an Anti- No-Flow
(3C7A)
RUN
Y2-24
Anti-No-Flow Detection
Time
(3C7B)
RUN
Y2-25
Anti-No-Flow Release
Level
(3C7C)
RUN
Y4: Application Advanced
No.
Name
(Hex.)
Y4-01
Pre-Charge Level
(3CFA)
RUN
Y4-02
Pre-Charge Frequency
(3CFB)
RUN
Y4-03
Pre-Charge Time
(3CFC)
RUN
Y4-05
Pre-Charge Loss of Prime
Level
(3CFE)
RUN
Y4-11
Thrust Acceleration Time Sets the time at which the drive output frequency will ramp up to the reference frequency
(3D04)
RUN
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Description
Sets the delay time before the drive enters Sleep Mode when the drive is at the sleep level
set in Y2-02 [Sleep Level].
Sets the level above which the output frequency must increase to activate the Sleep
Function when Y2-01 = 0, 3, or 5 [Sleep Level Type = Output Frequency, Output Speed
(RPM), or Output Frequency (non-PID)].
Note:
When you set this parameter to 0.0, this function will not be active, and the Sleep
Function will activate above the minimum speed (largest value from d2-02 [Frequency
Reference Lower Limit], Y1-06 [Minimum Speed], and Y4-12 [Thrust Frequency]).
Sets the quantity of boost that the drive applies to the setpoint before it goes to sleep.
Note:
Set this parameter to 0.00 to disable Sleep Boost Function.
Sets the length of time that the drive will keep the boosted pressure before it goes to sleep.
Sets the length of time that the system (feedback) has to reach the boosted setpoint. The
system must reach the boosted setpoint in the time set in this parameter, or it will go to
sleep.
Sets the level of the PID Error (set-point minus feedback) to deactivate the Sleep Mode
operation.
Note:
Set this parameter to 0.00 to disable the function.
Sets the time during which the software monitors the feedback to detect a flow/no-flow
condition. Refer to Y2-08 [Delta Feedback Drop Level] for more information.
condition.
Note:
Do not set this parameter value too high, because operation can become unstable.
Sets the time delay before the drive starts the increased deceleration rate after it detects
Anti-No-Flow.
Sets the amount below the setpoint which the feedback must decrease before the drive will
disengage Anti-No-Flow and return to normal PI operation.
Note:
The display unit and scaling change when the System Units change.
Description
Sets the level at which the drive will activate the pre-charge function when the drive is
running at the frequency set in Y4-02 [Pre-Charge Frequency].
Note:
The drive will stop when one of these conditions is true:
• The feedback level increases to more than Y4-01
• The pre-charge time set in Y4-03 [Pre-Charge Time] expires
Sets the frequency at which the pre-charge function will operate.
Sets the length of time that the Pre-Charge function will run.
Note:
Set this parameter to 0.0 to disable the function.
Sets the level at which the drive will detect loss of prime in the pump.
set in Y4-12 [Thrust Frequency].
9.16 Y: Application Features
Default
Ref.
(Range)
5 s
413
(0 - 3600 s)
0.0
413
(0.0 - 6000.0)
0.00%
413
(0.00 - 600.00%)
5.0 s
414
(0.5 - 160.0 s)
20.0 s
414
(1.0 - 160.0 s)
0.00%
414
(0.00 - 600.00%)
10.0 s
414
(0.0 - 3600.0 s)
0.00%
414
(0.00 - 2.00%)
10.0 s
414
(1.0 - 60.0 s)
0.30%
415
(0.00 - 10.00%)
Default
Ref.
(Range)
0.00%
415
(0.00 - 600.00%)
0.0 Hz
415
(0.0 - 400.0 Hz)
0.0 min
415
(0.0 - 3600.0 min)
0.0 A
415
(0.0 - 1000.0 A)
1.0 s
415
(0.0 - 600.0 s)
9
659