Checking Modified Parameters - YASKAWA HV600 Technical Reference

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

4.4 Keypad Operation
4.
Push
or
5.
Push
or
6.
Push
or
The keypad will show the "End" message when the write process is complete.

Checking Modified Parameters

Modified Parameters Screen Displays
The keypad display for Modified Parameters screen changes when A1-06 [Application Preset] changes:
A1-06 Settings
0
1 - 8
Check Modified Parameters
This procedure will show all parameters that are not at their default values. This helps find settings have been
changed, and is very useful when you replace a drive. This lets you quickly access and re-edit changed parameters.
The keypad will show "0 Parameters" when all parameters are at their default values.
150
to select the item to verify, then push
to select [Delete (keypad)], then push
to select the data to delete, then push
Keypad Display
When you set A1-06 = 0 [No Preset Selected], the Modified Parameters screen will only show
[Standard].
When you set an application macro (A1-06 ≠ 0), the Modified Parameters screen will show the Standard
menu and Application Presets menu.
• Standard: This menu shows all parameters modified by the A1-06 setting and any standard drive
• Application Presets: This menu only shows parameters not set by A1-06.
.
.
.
parameters modified after you changed the A1-06 setting.
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Description