YASKAWA HV600 Technical Reference page 721

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

CMD REV.STOP (Point 22) can be commanded to run the bypass in the reverse direction. FWD.REV (Point 21)
shows the current direction of the bypass rotation.
NOTICE: Damage to Equipment. Make sure that the motor direction is correct when you set b1-04 = 0 [Reverse Operation
Selection = Reverse Enabled]. Incorrect motor direction can cause damage to HVAC equipment.
• Lock the Bypass Panel
Locking the panel prevents the user from using the HAND and OFF keys locally at the drive panel. LOCK PANEL
(Point 33) can be commanded to lock and unlock the panel.
• Digital Outputs
MULTI OUT 1 (Point 40), MULTI OUT 2 (Point 41), and MULTI OUT 3 (Point 42) are physical digital outputs on
the bypass. Their purpose depends on how the bypass has been set-up. The bypass can be programmed so that these
points can display various limits, warnings, and status conditions. Some examples include frequency limit, over
current, and motor over temperature fault.
• Loop Gain
PID P GAIN (Point 63) and PID I TIME (Point 64) are the gain and integral time parameters similar to the P and I
gains in the APOGEE FLN Terminal Equipment Controllers. The PI loop of the drive is structured differently than
the Siemens loop, so there is not a one-to-one correspondence between the gains.
• Reading and Resetting Faults
OK.FAULT (Point 93) shows the current status of the drive. FAULT CODE (Point 17) contains the code for the
most current fault. LST FLT CODE (Point 66) contains the code for the previous fault. See table below for
descriptions of the fault codes. The drive can be reset back to OK mode by commanding RESET FAULT (Point 94)
to RESET.
APOGEE FLN Point Database
This section shows the APOGEE FLN point database for Application 2721.
APOGEE FLN Point List Summary
This database is for APOGEE FLN Application 2721 and features 92 logical points: 29 Logical Analog Inputs (LAI),
31 Logical Analog Outputs (LAO), 19 Logical Digital Inputs (LDI) and 13 Logical Digital Outputs (LDO). These
points set, control, or monitor the operation of the drive.
Information to consider when referencing this table:
1. This application does not use the points that are not listed.
2. A single value in a column means that the value is the same in English units and in SI units.
Point
Point
Point Name
No.
Type
01
LAO
CTLR ADDRESS
02
LAO
APPLICATION
*1
03
LAI
FREQ OUTPUT
*1
04
LAI
PCT OUTPUT
*1
05
LAI
SPEED
*1
06
LAI
CURRENT
*1
07
LAI
TORQUE
*1
08
LAI
POWER
*1
09
LAI
DRIVE TEMP
*1
10
LAI
DRIVE KWH
*1
11
LAI
*1
12
LAI
RUN TIME
*1
13
LAI
DC BUS VOLT
*1
14
LAI
AC OUT VOLT
15
LAI
PAR N9.01
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Table 10.10 APOGEE FLN Application 2721 Point Number Summary
Factory
Eng. Units
Default
(SI Units)
31
2721
0
0
0
0
0
0
0
0
MWH
0
0
0
0
0
10.4 APOGEE FLN (P1) Communications
Slope
Intercept
(SI Units)
(SI Units)
(SI Units)
-
1
-
1
Hz
0.01
%
0.01
RPM
0.01
A
0.01/0.1
%
0.1
kW
0.1
° C/F
1
kWh
0.1
mWh
1
h
1
V
1
V
0.1
A
0.01/0.1
On Text
Off Text
0
-
-
0
-
-
0
-
-
0
-
-
0
-
-
0
-
-
0
-
-
0
-
-
0
-
-
0
-
-
0
-
-
0
-
-
0
-
-
0
-
-
0
-
-
Parameter
H5-01
-
U1-02
-
-
UB-01
-
U1-08
U4-08
U4-10
U4-11
10
U4-01
U1-07
U1-06
-
721

Advertisement

Table of Contents
loading

Table of Contents