9.13 o: Keypad-Related Settings
◆
o5: Log Function
No.
Name
(Hex.)
o5-01
Log Start/Stop Selection
(1551)
RUN
o5-02
Log Sampling Interval
(1552)
RUN
o5-03
Log Monitor Data 1
(1553)
RUN
o5-04
Log Monitor Data 2
(1554)
RUN
o5-05
Log Monitor Data 3
(1555)
RUN
o5-06
Log Monitor Data 4
(1556)
RUN
o5-07
Log Monitor Data 5
(1557)
RUN
o5-08
Log Monitor Data 6
(1558)
RUN
o5-09
Log Monitor Data 7
(1559)
RUN
o5-10
Log Monitor Data 8
(155A)
RUN
o5-11
Log Monitor Data 9
(155B)
RUN
o5-12
Log Monitor Data 10
(155C)
RUN
646
Sets the data log function. This parameter is only available on an HOA keypad.
0 : OFF
1 : ON
Note:
You must insert a compatible SD cart into the keypad before you enable this parameter.
Sets the data log sampling cycle. This parameter is only available on an HOA keypad.
Sets the data log monitor. This parameter is only available on an HOA keypad.
Sets the data log monitor. This parameter is only available on an HOA keypad.
Sets the data log monitor. This parameter is only available on an HOA keypad.
Sets the data log monitor. This parameter is only available on an HOA keypad.
Sets the data log monitor. This parameter is only available on an HOA keypad.
Sets the data log monitor. This parameter is only available on an HOA keypad.
Sets the data log monitor. This parameter is only available on an HOA keypad.
Sets the data log monitor. This parameter is only available on an HOA keypad.
Sets the data log monitor. This parameter is only available on an HOA keypad.
Sets the data log monitor. This parameter is only available on an HOA keypad.
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
Ref.
(Range)
0
372
(0 - 1)
100 ms
372
(100 - 60000 ms)
101
372
(000, 101 - 1299)
102
373
(000, 101 - 1299)
103
373
(000, 101 - 1299)
107
373
(000, 101 - 1299)
108
373
(000, 101 - 1299)
0
373
(0, 101 - 1299)
000
374
(000, 101 - 1299)
000
374
(000, 101 - 1299)
000
374
(000, 101 - 1299)
000
374
(000, 101 - 1299)