YASKAWA HV600 Technical Reference page 406

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

5.12 T: Auto-Tuning
T1-04: Motor Rated Current
No.
Name
(Hex.)
T1-04
Motor Rated Current
(0704)
Set the motor rated current between 50% and 100% of the drive rated current for the best performance. Enter the
current at the motor base speed.
T1-05: Motor Base Frequency
No.
Name
(Hex.)
T1-05
Motor Base Frequency
(0705)
When you do Auto-Tuning, the drive sets T1-05 to E1-04 [Maximum Output Frequency]. If T1-05 < 40 Hz, E1-04 =
40 Hz. If you operate the drive at a speed that is higher than the base frequency, or if you operate in the field
weakening range, set E1-04 to the maximum output frequency after you complete Auto-Tuning.
T1-06: Number of Motor Poles
No.
Name
(Hex.)
T1-06
Number of Motor Poles
(0706)
T1-07: Motor Base Speed
No.
Name
(Hex.)
T1-07
Motor Base Speed
(0707)
T1-11: Motor Iron Loss
No.
Name
(Hex.)
T1-11
Motor Iron Loss
(070B)
Note:
The default setting is different for different motor codes and motor parameter settings.
The value shown is the E2-10 [Motor Iron Loss] for the motor output set in T1-02 [Motor Rated Power]. If the motor
test report is available, enter the motor iron loss value to T1-11.
406
Sets the rated current (A) of the motor.
Sets the base frequency (Hz) of the motor.
Sets the number of motor poles.
Sets the motor base speed for Auto-Tuning (min
Sets the iron loss for calculating the energy-saving coefficient.
Description
Description
Description
Description
-1
(r/min)).
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
(Range)
Determined by o2-04
(10% to 200% of the drive
rated current)
Default
(Range)
60.0 Hz
(0.0 - 400.0 Hz)
Default
(Range)
4
(2 to 120)
Default
(Range)
-1
1750 min
(r/min)
(0 - 24000 min
-1
(r/min))
Default
(Range)
Determined by E2-11
(0 - 65535 W)

Advertisement

Table of Contents
loading

Table of Contents