5.11 S: Special Applications
10 : °C: Celsius
11 : m: meters
12 : ft: feet
13 : L/min: liters/min
3
14 : m
/min: cubic meters/min
15 : "Hg: Inch Mercury
16 : kPa: kilopascal
48 : %: Percent
49 : Custom(b5-68~70)
50 : None
S6-05: EMOVR Independent PID Unit Digit
No.
Name
(Hex.)
S6-05
EMOVR Independent PID
Unit Digit
(323C)
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
S6-06: EMOVR PID Setpoint
No.
Name
(Hex.)
S6-06
EMOVR PID Setpoint
(323D)
RUN
Note:
When S6-02 = 3: units and resolution are dependent on S6-04 [EMOVR Independent PID Unit] and S6-05 [EMOVR Independent PID Unit
Digit]. Value is internally limited to 300% of S6-03 [EMOVR Independent PID Scale].
S6-07: EMOVR Fault Suppression Mode
No.
Name
(Hex.)
S6-07
EMOVR Fault Suppression
Mode
(323E)
0 : Fault Suppression
1 : Test Mode
S6-08: EMOVR Drive Enable Input Mode
No.
Name
(Hex.)
S6-08
EMOVR Drive Enable Input
Mode
(323F)
0 : Drive Enable Status Ignored
1 : EMOVRun Only When Drive Disabled
Note:
You must program Drive Enable to a Digital Input for this parameter to have an effect.
400
Sets the number of digits for S6-06 [EMOVR PID Setpoint] when S6-02 = 3[Emergency Override
Ref Selection = Independent PID Mode].
Sets the PID Setpoint when S6-02 = 3[Emergency Override Ref Selection = Independent PID Mode].
Sets the drive to let Emergency Override disable faults during operation.
Sets whether the Drive Enable Input (if programmed) must be inactive (drive is disabled) for
Emergency Override to function.
Description
Description
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
(Range)
2
(0 - 3)
Default
(Range)
0.00
(0 - 600.00)
Default
(Range)
0
(0, 1)
Default
(Range)
0
(0, 1)