5.14 Z: Bypass Parameters
VFD RUN COMMAND
DAMPER ACTUATOR OUTPUT
BAS INTERLOCK INPUT
VFD FREQUENCY REFERENCE
VFD OUTPUT FREQUENCY
FAULT: FB02 BAS Ilock Open
Figure 5.100 Run Delay with Preset Speed Example: BAS Interlock Wait Time Fault
DAMPER ACTUATOR OUTPUT
VFD FREQUENCY REFERENCE
Z1-14 Run Delay Frequency Reference
VFD OUTPUT FREQUENCY
432
1 t
VFD RUN COMMAND
BAS INTERLOCK INPUT
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Interlock Run Select = 1 (Enable)
Z1-14 Run Delay Frequency Reference = 30.0 Hz
Z1-15 Interlck Wait Time = 0.0 sec (Never Time Out)
Figure 5.101 Run Delay with Preset Speed Example: Preset Speed
Z1-15 Interlock Wait Time
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Interlock Run Select = 0 (Disabled)
Z1-14 Run Delay Frequency Reference = 60.0 Hz
Z1-15 Interlck Wait Time = 10.0 sec
t1
t2
t3
t4
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
2 t
t3