YASKAWA HV600 Technical Reference page 259

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

F7-17: EtherNet/IP Speed Scaling Factor
No.
Name
(Hex.)
F7-17
EtherNet/IP Speed Scaling
Factor
(03F5)
F7-18: EtherNet/IP Current Scale Factor
No.
Name
(Hex.)
F7-18
EtherNet/IP Current Scale
Factor
(03F6)
F7-19: EtherNet/IP Torque Scale Factor
No.
Name
(Hex.)
F7-19
EtherNet/IP Torque Scale
Factor
(03F7)
F7-20: EtherNet/IP Power Scaling Factor
No.
Name
(Hex.)
F7-20
EtherNet/IP Power Scaling
Factor
(03F8)
F7-21: EtherNet/IP Voltage Scale Factor
No.
Name
(Hex.)
F7-21
EtherNet/IP Voltage Scale
Factor
(03F9)
F7-22: EtherNet/IP Time Scaling
No.
Name
(Hex.)
F7-22
EtherNet/IP Time Scaling
(03FA)
F7-23 to F7-32: Dynamic Out Param 1 to 10 for CommCard
No.
Name
(Hex.)
F7-23 to F7-27
Dynamic Out Param 1 to 10
for CommCard
(03FB - 03FF)
F7-28 to F7-32
(0370 - 0374)
F7-33 to F7-42: Dynamic In Param 1 to 10 for CommCard
No.
Name
(Hex.)
F7-33 to F7-42
Dynamic In Param 1 to 10
for CommCard
(0375 - 037E)
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Sets the scaling factor for the speed monitor in the EtherNet/IP Class ID 2AH Object.
Sets the scaling factor for the output current monitor in the EtherNet/IP Class ID 2AH Object.
Sets the scaling factor for the torque monitor in the EtherNet/IP Class ID 2AH Object.
Sets the scaling factor for the power monitor in the EtherNet/IP Class ID 2AH Object.
Sets the scaling factor for the voltage monitor in the EtherNet/IP Class ID 2AH Object.
Sets the scaling factor for the time monitor in the EtherNet/IP Class ID 2AH Object.
When you use an Ethernet/IP option, sets Output Assembly 116. The drive writes the values from
Output Assembly 116 to the MEMOBUS/Modbus address register that is stored for each parameter.
The drive will not write the values from Output Assembly 116 to the registers when the MEMOBUS/
Modbus address is 0. When you use a ProfiNet option, set F7-23 to F7-27 to configurable Output 1-
5.
When you use an Ethernet/IP option, sets Input Assembly 166. The drive sends the values from the
MEMOBUS/Modbus address registers stored for each parameter to Input Assembly 166. The drive
returns the default register value for the option card when the MEMOBUS/Modbus address is 0 and
the value sent to Input Assembly 166 is not defined. When you use a ProfiNet option, set F7-33 to
F7-37 to configurable inputs 1-5.
Description
Description
Description
Description
Description
Description
Description
Description
5.6 F: Options
Default
(Range)
0
(-15 - +15)
Default
(Range)
0
(-15 - +15)
Default
(Range)
0
(-15 - +15)
Default
(Range)
0
(-15 - +15)
Default
(Range)
0
(-15 - +15)
Default
(Range)
0
(-15 - +15)
5
Default
(Range)
0
Default
(Range)
0
259