Control Circuit Wire Gauges and Tightening Torques
Use the tables in this section to select the correct wires. Use shielded wire to wire the control circuit terminal block.
Use crimp ferrules on the wire ends to make the wiring procedure easier and more reliable.
Drive
Terminal
Terminal
Block
TB1
+V, AC, A1, A2, FM
TB3
AM, AC, S1 - S7
TB4
SN, SC, SP, +P
TB5
SN, HC, H1, H2
TB6
AC, D+, D-, PS
TB7
MA, MB, MC, M1 - M6
TB2
FE
100
Table 3.20 Control Circuit Wire Gauges and Tightening Torques
Tightening Torque
Screw Size
N∙m (in∙lb)
0.5 - 0.6
(4.4 - 5.3)
M3
1.0 - 1.2
(8.85 - 10.62)
Bare Wire
Recommended
Applicable Gauge
Gauge
2
mm
(AWG)
mm
2
(AWG)
Stranded wire:
0.25 - 1.5
0.75
(24 - 16)
(18)
Solid wire:
0.25 - 1.5
(24 - 16)
Stranded wire:
0.12 - 0.75
0.75
(26 - 18)
(18)
Solid wire:
0.2 - 1.5
(26 - 16)
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Crimp Ferrule
Recommended
Applicable Gauge
Gauge
2
mm
(AWG)
mm
2
(AWG)
0.75
0.25 - 1.5
(18)
(24 - 16)
0.75
0.25 - 1.5
(18)
(24 - 16)

Advertisement