YASKAWA HV600 Technical Reference page 246

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

5.5 E: Motor Parameters
D002 - D016, A002 - A015, B001 - B007
4 : VT, 50Hz, 65% Vmid reduction
Use this derated torque pattern for torque loads proportional to three times the rotation speed. For example, fans and
pumps.
Note:
The voltage values in the figures are for 208/240 V. Multiply the values by 2 for 480 V.
D002 - D016, A002 - A015, B001 - B007
5 : VT, 50Hz, 50% Vmid reduction
Use this derated torque pattern for torque loads proportional to two times the rotation speed. For example, fans and
pumps.
Note:
The voltage values in the figures are for 208/240 V. Multiply the values by 2 for 480 V.
D002 - D016, A002 - A015, B001 - B007
6 : VT, 60 Hz, 65% Vmid reduction
Use this derated torque pattern for torque loads proportional to three times the rotation speed. For example, fans and
pumps.
Note:
The voltage values in the figures are for 208/240 V. Multiply the values by 2 for 480 V.
D002 - D016, A002 - A015, B001 - B007
7 : VT, 60Hz, 50% Vmid reduction
246
D024 - D169, A022 - A154, B011 - B077
D024 - D169, A022 - A154, B011 - B077
D024 - D169, A022 - A154, B011 - B077
D024 - D169, A022 - A154, B011 - B077
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
A192 - A248, B096 - B302
A192 - A248, B096 - B302
A192 - A248, B096 - B302
A192 - A248, B096 - B302