5.3 C: Tuning
Note:
When the wiring length for bypass models B001 to B007 is more than 10 m, you must decrease the carrier frequency or output current.
C6-03: Carrier Frequency Upper Limit
No.
Name
(Hex.)
C6-03
Carrier Frequency Upper
Limit
(0225)
Setting a Fixed User-Defined Carrier Frequency
When you cannot use C6-02 to set a carrier frequency between set selectable values, you can set the value in C6-03.
The carrier frequency will be fixed to the value set to C6-03.
Set C6-03 = C6-04 [Carrier Frequency Lower Limit] to fix the carrier frequency.
Setting a Variable Carrier Frequency to Agree with the Output Frequency
Set C6-03, C6-04, and C6-05 [Carrier Freq Proportional Gain] as shown in
frequency change linearly with the output frequency.
C6-03: Carrier Frequency Upper Limit
C6-04: Carrier Frequency Lower Limit
Figure 5.31 Setting a Variable Carrier Frequency to Agree with the Output Frequency
Note:
• When C6-05 ≤ 7, the drive disables C6-04. The carrier frequency is fixed to the value set to C6-03.
• If these conditions are true at the same time, the drive will detect oPE11 [Carrier Frequency Setting Error]:
–C6-05 ≥ 6
–C6-04 ≥ C6-03
C6-04: Carrier Frequency Lower Limit
No.
Name
(Hex.)
C6-04
Carrier Frequency Lower
Limit
(0226)
Set C6-03 [Carrier Frequency Upper Limit], C6-04, and C6-05 [Carrier Freq Proportional Gain] to make the carrier
frequency change linearly with the output frequency.
Note:
If these conditions are true at the same time, the drive will detect oPE11 [Carrier Frequency Setting Error]:
• C6-04 ≥ C6-03
• C6-05 ≥ 6
C6-05: Carrier Freq Proportional Gain
No.
Name
(Hex.)
C6-05
Carrier Freq Proportional
Gain
(0227)
Set C6-03 [Carrier Frequency Upper Limit], C6-04 [Carrier Frequency Lower Limit], and C6-05 to make the carrier
frequency change linearly with the output frequency.
232
Sets the upper limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)] to set this parameter.
Sets the lower limit of the carrier frequency. Set C6-02 = F [Carrier Frequency Selection = User
Defined (C6-03 to C6-05)] to set this parameter.
Sets the proportional gain for the carrier frequency. Set C6-02 = F [Carrier Frequency Selection =
User Defined (C6-03 to C6-05)] to set this parameter.
Description
Figure 5.31
C6-05: Carrier Freq Proportional Gain
E1-04: Maximum Output Frequency
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
(Range)
Determined by C6-02
(1.0 - 12.5 kHz)
to make the carrier
Default
(Range)
Determined by C6-02
(1.0 - 12.5 kHz)
Default
(Range)
Determined by C6-02
(0 - 99)