YASKAWA HV600 Technical Reference page 273

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

85: Dedicated Multi-Setpoint YA-04
Setting Value
Function
85
Dedicated Multi-Setpoint
YA-04
Note:
If you use this function and one of H1-xx = 3E or 3F [PID Setpoint Selection 1 or 2] at the same time, the drive will detect an oPE03 [Multi-
Function Input Setting Err].
ON : YA-04 is PID setpoint.
OFF : YA-01 [Setpoint 1], YA-02 [Setpoint 2], or YA-03 [Setpoint 3] is PID setpoint.
88: Thermostat Fault
Setting Value
Function
88
Thermostat Fault
Note:
This function is active when the drive is running.
If the drive is running in AUTO Mode or HAND Mode and if the terminal set for H1-xx = 88 [MFDI Function
Selection = Thermostat Fault] is ON or if the terminal set for H1-xx = 188 [!Thermostat Fault] is OFF, the drive will
detect VLTS.
A8: PI2 Control Disable
Setting Value
Function
A8
PI2 Control Disable
ON : Enabled
OFF : Disabled
AA: PI2 Control Inverse Operation
Setting Value
Function
AA
PI2 Control Inverse
Operation
AB: PI2 Control Integral Reset
Setting Value
Function
AB
PI2 Control Integral Reset
AC: PI2 Control Integral Hold
Setting Value
Function
AC
PI2 Control Integral Hold
AD: Select PI2 Control PI Parameters
Setting Value
Function
AD
Select PI2 Control PI
Parameters
B9: Disable Pre-charge
Setting Value
Function
B9
Disable Pre-charge
ON : Pre-charge function is disabled
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Sets the function to set the PID setpoint to YA-04 [Setpoint 4]. Set this function, H1-xx = 83 [Dedicated Multi-Setpoint YA-02], and
H1-xx = 84 [Dedicated Multi-Setpoint YA-03] at the same time.
Sets the drive to show the VLTS [Thermostat Fault] when the input terminal is ON.
Sets the command to disable the PI2 Control function. Parameter S3-12 [PI2 Control Disable Mode Sel] sets the output
performance.
Sets the command to change the sign of the PI2 Control input.
Sets the command to reset the PI2 Control integral value.
Sets the command to lock the PI2 Control integral value.
Sets the command to use the S3-06 [PI2 Control Proportional Gain] and S3-07 [PI2 Control Integral Time] values instead of the
b5-02 [Proportional Gain (P)] and b5-03 [Integral Time (I)] values. Set S3-01 = 0 [PI2 Control Enable Selection = Disabled] to
enable this function.
Sets the command to disable the Pre-charge function.
5.7 H: Terminal Functions
Description
Description
Description
Description
Description
Description
Description
Description
5
273