YASKAWA HV600 Technical Reference page 600

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

9.5 b: Application
No.
Name
(Hex.)
b3-17
Speed Est Retry Current
Level
(01F0)
Expert
b3-18
Speed Est Retry
Detection Time
(01F1)
Expert
b3-19
Speed Search Restart
Attempts
(01F2)
b3-24
Speed Search Method
Selection
(01C0)
b3-25
Speed Search Wait Time
(01C8)
Expert
b3-26
Direction Determination
Level
(01C7)
Expert
b3-27
Speed Search RUN/BB
Priority
(01C9)
Expert
b3-31
Spd Search Current
Reference Lvl
(0BC0)
Expert
b3-32
Spd Search Current
Complete Lvl
(0BC1)
Expert
b3-33
Speed Search during Uv
Selection
(0B3F)
Expert
b3-56
InverseRotationSearch
WaitTime
(3126)
b4: Timer Function
No.
Name
(Hex.)
b4-01
Timer Function ON-
Delay Time
(01A3)
b4-02
Timer Function OFF-
Delay Time
(01A4)
b4-03
Terminal M1-M2 ON-
Delay Time
(0B30)
Expert
b4-04
Terminal M1-M2 OFF-
Delay Time
(0B31)
Expert
b4-05
Terminal M3-M4 ON-
Delay Time
(0B32)
Expert
b4-06
Terminal M3-M4 OFF-
Delay Time
(0B33)
Expert
600
Sets the current level for the search retry function in Speed Estimation Speed Search as a
percentage where drive rated current is a setting value of 100%.
Sets the length of time that the drive will wait to retry Speed Estimation Speed Search
when too much current flow stopped the Speed Search.
Sets the number of times to restart Speed Search if Speed Search does not complete.
Sets the Speed Search method when you start the motor or when you return power after a
momentary power loss.
Note:
Set b3-24 = 1. If b3-24 = 2, the drive will detect oPE08 [Parameter Selection Error].
1 : Speed Estimation
2 : Current Detection 2
Sets the length of time the drive will wait to start the Speed Search Retry function.
Sets the level to find the motor rotation direction. Increase the value if the drive cannot
find the direction.
Sets the conditions necessary to start Speed Search.
0 : SS Only if RUN Applied Before BB
1 : SS Regardless of RUN/BB Sequence
Sets the current level that decreases the output current during Current Detection Speed
Search.
Sets the current level that completes Speed Search.
Sets the function that starts Speed Search at start-up if the drive detects a Uv
[Undervoltage] when it receives a Run command.
0 : Disabled
1 : Enabled
Sets the wait time until the drive starts inverse rotation search after it completes forward
search when you do inverse rotation search during Current Detection Speed Search.
Sets the ON-delay time for the timer input.
Sets the OFF-delay time for the timer input.
Sets the delay time to activate the contact after the function set in H2-01 activates.
Sets the delay time to deactivate the contact after the function set in H2-01 deactivates.
Sets the delay time to activate the contact after the function set in H2-02 activates.
Sets the delay time to deactivate the contact after the function set in H2-02 deactivates.
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
Ref.
(Range)
110%
204
(0 - 200%)
0.10 s
204
(0.00 - 1.00 s)
3 times
204
(0 - 10 times)
2
204
(1, 2)
0.5 s
205
(0.0 - 30.0 s)
1000
205
(40 to 60000)
0
205
(0, 1)
1.50
205
(1.50 - 3.50)
1.20
205
(0.00 - 1.49)
1
206
(0, 1)
Determined by o2-04
206
(0.1 - 5.0 s)
Default
Ref.
(Range)
0.0 s
207
(0.0 - 3000.0 s)
0.0 s
207
(0.0 - 3000.0 s)
0 ms
207
(0 - 65000 ms)
0 ms
207
(0 - 65000 ms)
0 ms
207
(0 - 65000 ms)
0 ms
207
(0 - 65000 ms)