YASKAWA HV600 Technical Reference page 435

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

Note:
Actual values depend on unit settings of drive parameters o1-03, o1-09, o1-10, and o1-11.
Z1-18: Energy Savings Output Cur Level
No.
Name
(Hex.)
Z1-18
Energy Savings Output Cur
Level
(85D7)
Z1-19: Energy Savings Fref Deadband
No.
Name
(Hex.)
Z1-19
Energy Savings Fref
Deadband
(85D8)
Z1-20: Energy Savings Out Freq Deadband
No.
Name
(Hex.)
Z1-20
Energy Savings Out Freq
Deadband
(85D9)
Z1-21: Energy Savings Out Cur Deadband
No.
Name
(Hex.)
Z1-21
Energy Savings Out Cur
Deadband
(85DA)
Z1-22: Energy Savings Mode Time
No.
Name
(Hex.)
Z1-22
Energy Savings Mode Time
(85DB)
Z1-23: Energy Savings Freq Ref Increase
No.
Name
(Hex.)
Z1-23
Energy Savings Freq Ref
Increase
(85DC)
Note:
Actual values depend on unit settings of drive parameters o1-03, o1-09, o1-10, and o1-11.
Z1-24: Contactor Open Delay
No.
Name
(Hex.)
Z1-24
Contactor Open Delay
(85DD)
Z1-25: Contactor Close Delay
No.
Name
(Hex.)
Z1-25
Contactor Close Delay
(85DE)
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Lets the system switch when the output current is more than this level of motor rated current for the
time set in Z1-22, Energy Time.
Sets the tolerance around the drive frequency reference value during comparisons to enter or exit
Energy Savings Mode.
Sets the tolerance around the drive output frequency value during comparisons to enter or exit Energy
Savings Mode.
Sets the tolerance around the drive output current value during comparisons to enter or exit Energy
Savings Mode as a percentage of motor rated current.
Sets the length of time that the drive frequency reference and drive output frequency must be in the
set limits before transferring to Energy Savings Mode.
Sets the value to add to the drive Frequency Reference when transferring to Bypass Energy Savings
Mode.
Sets the time to delay after commanding the drive output contactor K2 or bypass contactor K3 or 2-
Motor OR/AND contactors K4 and K5 to open to let the contacts open.
Sets the time to delay after commanding the drive output contactor K2 or bypass contactor K3 or 2-
Motor OR/AND contactors K4 and K5 to close to let the contacts close.
Description
Description
Description
Description
Description
Description
Description
Description
5.14 Z: Bypass Parameters
Default
(Range)
0.0%
(0.0 - 100.0%)
Default
(Range)
0.50 Hz
(0.00 - 5.00 Hz)
Default
(Range)
0.50 Hz
(0.00 - 5.00 Hz)
Default
(Range)
15.0%
(0.0 - 30.0%)
Default
(Range)
30 s
(10 - 3600 s)
Default
(Range)
6.00 Hz
(0.00 - 10.00 Hz)
Default
(Range)
0.2 s
(0.0 - 5.0 s)
Default
(Range)
0.2 s
(0.0 - 5.0 s)
5
435