YASKAWA HV600 Technical Reference page 291

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

89: Output Current Lim
Setting Value
Function
89
Output Current Lim
94: Loss of Prime
Setting Value
Function
94
Loss of Prime
95: Thermostat Fault
Setting Value
Function
95
Thermostat Fault
96: High Feedback
Setting Value
Function
96
High Feedback
97: Low Feedback
Setting Value
Function
97
Low Feedback
9E: Low PI Auxiliary Control Level
Setting Value
Function
9E
Low PI Auxiliary Control
Level
9F: High PI Auxiliary Control Level
Setting Value
Function
9F
High PI Auxiliary Control
Level
A9: RELAY Operator Control
Setting Value
Function
A9
RELAY Operator Control
AB: Thrust Mode
Setting Value
Function
AB
Thrust Mode
AC: Setpoint Not Maintained
Setting Value
Function
AC
Setpoint Not Maintained
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
The terminal activates when the output current limit is limiting the drive output speed.
The terminal activates when the drive is in an LOP [Loss of Prime] condition.
The terminal activates when the terminal set for H1-xx = 88 [MFDI Function Selection = Thermostat Fault] is active.
The terminal activates when the drive is in a High Feedback Condition as specified by Y1-11 [High Feedback Level] and Y1-12
[High Feedback Lvl Fault Dly Time] and when the drive detects an HFB [High Feedback Sensed] fault or an HIFB [High Feedback
Sensed] alarm.
The terminal activates when the drive is in a Low Feedback Condition as specified by Y1-08 [Low Feedback Level] and Y1-09 [Low
Feedback Lvl Fault Dly Time] and when the drive detects an LFB [Low Feedback Sensed] fault or an LOFB [High Feedback
Sensed] alarm.
The terminal activates when the PI Aux Feedback Level is less than YF-09 [PI Aux Control Low Level Detect] or if the drive detects
an LOAUX [Low PI Aux Feedback Level] fault.
The terminal activates when the PI Aux Feedback Level is more than YF-12 [PI Aux Control High Level Detect] or if the drive
detects an HIAUX [High PI Aux Feedback Level] fault.
The terminal changes to OFF or ON when you push the RELAY (
it OFF. When the terminal is OFF, push
The terminal activates when the output frequency is between 0.0 Hz and the value set in Y4-12 [Thrust Frequency] and the Thrust
Bearing function is active.
The terminal activates when the drive detects NMS [Setpoint Not Met] condition.
5.7 H: Terminal Functions
Description
Description
Description
Description
Description
Description
Description
Description
) button. When the terminal is ON, push
to turn in ON.
Description
Description
5
to turn
291