D002 - D016, A002 - A015, B001 - B007
E : Const Trq, 60 Hz base, 180 Hz max
Use this constant output pattern to rotate motors at more than 60 Hz. Output voltage is constant when you operate at
more than 60 Hz.
Note:
The voltage values in the figures are for 208/240 V. Multiply the values by 2 for 480 V.
D002 - D016, A002 - A015, B001 - B007
F : Custom
Set E1-04 to E1-13 [V/f Pattern for Motor 1] to set the values for this custom pattern.
The default settings are the same as setting value 1 [Const Trq, 60Hz base, 60Hz max].
E1-04: Maximum Output Frequency
No.
Name
(Hex.)
E1-04
Maximum Output Frequency Sets the maximum output frequency for the V/f pattern.
(0303)
E1-05: Maximum Output Voltage
No.
Name
(Hex.)
E1-05
Maximum Output Voltage
(0304)
E1-06: Base Frequency
No.
Name
(Hex.)
E1-06
Base Frequency
(0305)
E1-07: Mid Point A Frequency
No.
Name
(Hex.)
E1-07
Mid Point A Frequency
(0306)
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
D024 - D169, A022 - A154, B011 - B077
D024 - D169, A022 - A154, B011 - B077
Sets the maximum output voltage for the V/f pattern.
Sets the base frequency for the V/f pattern.
Sets a middle output frequency for the V/f pattern.
Description
Description
Description
Description
5.5 E: Motor Parameters
A192 - A248, B096 - B302
A192 - A248, B096 - B302
Default
(Range)
60.0 Hz
(40.0 to 400.0 Hz)
Default
(Range)
208/240 V: 230.0 V,
480 V: 460.0 V
(208/240 V: 0.0 - 255.0 V,
480 V: 0.0 - 510.0 V)
Default
(Range)
60.0 Hz
(0.0 - E1-04)
Default
(Range)
30.0 Hz
(0.0 - E1-04)