YASKAWA HV600 Technical Reference page 220

Ac drive bypass for hvac fan and pump applications
Hide thumbs Also See for HV600:
Table of Contents

Advertisement

5.2 b: Application
b5-44: PID Out2 Monitor MAX Lower4 Dig
No.
Name
(Hex.)
b5-44
PID Out2 Monitor MAX
Lower4 Dig
(0163)
RUN
Note:
Used for U5-14 [PID Out2 Upr4 Digits] and U5-15 [PID Out2 Lwr4 Digits] only.
b5-45: PID Out2 Monitor MIN for Linear
No.
Name
(Hex.)
b5-45
PID Out2 Monitor MIN for
Linear
(0164)
RUN
Note:
Used for U5-14 [PID Out2 Upr4 Digits] and U5-15 [PID Out2 Lwr4 Digits] only.
b5-46: PID Unit Display Selection
No.
Name
(Hex.)
b5-46
PID Unit Display Selection
(0165)
Refer to
System Units on page 212
0 : "WC: inches of water column
1 : PSI: pounds per square inch
2 : GPM: gallons/min
3 : °F: Fahrenheit
4 : ft
3
/min: cubic feet/min
5 : m
3
/h: cubic meters/hour
6 : L/h: liters/hour
7 : L/s: liters/sec
8 : bar: bar
9 : Pa: Pascal
10 : °C: Celsius
11 : m: meters
12 : ft: feet
13 : L/min: liters/min
14 : m
3
/min: cubic meters/min
15 : "Hg: Inch Mercury
16 : kPa: kilopascal
48 : %: Percent
49 : Custom(b5-68~70)
50 : None
220
Sets the lower 4 digits of the maximum monitor value. Used with b5-43 [PID Out2 Monitor MAX
Upper4 Dig] to set maximum monitor value of U5-14 [PID Out2 Upr4 Digits] and U5-15 [PID Out2
Lwr4 Digits] at maximum frequency.
Sets the minimum display value to show when at zero speed. Only effective when b5-42 = 0 [PID
Output 2 Calc Mode = Linear].
Sets the units-text for the PID Display.
for more information.
Description
Description
Description
YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Default
(Range)
0.00
(0.00 - 99.99)
Default
(Range)
0.0
(0.0 - 999.9)
Default
(Range)
48
(0 - 50)